Operating Instructions
Carry out zero point adjustment for relative and vacuum pressure measuring ranges in a
depressurized state.
Carry out zero point adjustment of absolute pressure ranges from 0 bar absolute (vacuum).
Since appropriate references are required for this, we recommend that this is only carried
out by the manufacturer.

6.4 Operating modes

System start
Display is fully activated for 2 seconds.
When the pressure switch is powered up within the range of the hysteresis, the output switch is set to
"not active" by default.

Display mode

Normal operation, display pressure value
Programming mode
Setting the parameters

6.5 Keys and functions

The pressure switch has two operating modes, the display mode and the programming mode. The selected
operating mode determines the respective function of the key.
MENU
INFO
MENU
3 8
O p e r a t i n g I n s t r u c t i o n s | S I C K
6. Commissioning, operation
Jumping into the programming mode
Keep the "MENU" key pressed for approx. 5 seconds. If the password is set to
≠ 0000, a password will be requested. If authentication is successful, then it enters
the programming mode, otherwise it reverts to display mode.
Returning to the display mode
Simultaneous pressing of both keys.