Spezifikationen
portsensor
portsensor all {field_list} show
portsensor {port_num} {field_list} show
portsensor {port_num} {energy_sensor} value
show
portsensor {port_num} counter reset
portsensor {port_num} {energy_sensor} events
set {OFF=0|ON=1}
portsensor {port_num} {energy_sensor} events
show
portsensor {port_num} {energy_sensor} events
type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2,E
VT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER=5,E
VT_DISPLAY=6,EVT_CONSOLE=7,EVT_MQTT=8}
"
portsensor {port_num} {energy_sensor} events
type show
portsensor {port_num} {energy_sensor} events
beeper mode set {CONTINOUS=0|
INTERMITTENT=1}
portsensor {port_num} {energy_sensor} events
beeper mode show
portsensor {port_num} {energy_sensor} maxval
set {num}
portsensor {port_num} {energy_sensor} maxval
show
portsensor {port_num} {energy_sensor} minval
set {num}
portsensor {port_num} {energy_sensor} minval
show
portsensor {port_num} {energy_sensor} hyst set
{num}
portsensor {port_num} {energy_sensor} hyst
show
portsensor {port_num} {energy_sensor} publish
mode set {NONE=0|INTERVAL=1|DELTA=2|
INTERV_DELTA=3}
portsensor {port_num} {energy_sensor} publish
mode show
portsensor {port_num} {energy_sensor} publish
mqtt retain set {OFF=0|ON=1}
portsensor {port_num} {energy_sensor} publish
mqtt retain show
portsensor {port_num} {energy_sensor} publish
timer set {num_secs}
portsensor {port_num} {energy_sensor} publish
timer show
portsensor {port_num} {energy_sensor} publish
delta set {float}
portsensor {port_num} {energy_sensor} publish
delta show
portsensor {port_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port set {port_num} set
portsensor {port_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state set {OFF=0|ON=1|
DISABLED=2}
portsensor {port_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port show
portsensor {port_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
95
Expert Power Control 8031/8035
enters cmd group "portsensor"
show s energy sensors according field list of all
port sensors
show s energy sensors according field list of one
port sensor
show s energy sensor of given port
resets energy metering counter
enables sensor events on/off
show s if sensor events are enabled
enables different event types
show s w hat event types are enabled
sets beeper tone
show s beeper tone
sets maximum value for sensor
show s maximum value for sensor
sets minimum value for sensor
show s minimum value for sensor
sets hysterese value for sensor
show s hysterese value for sensor
sets publish mode
show s publish mode
sets mqtt retain
show s if mqtt retain set
sets publish time interval
show s publish time interval
sets publish delta value
show s publish delta value
sets pow er port for sensor values action
sets state for sensor values action
show s port for sensor values action
show s state for sensor values action
5
5
5
© 2022 GUDE Systems GmbH