Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection; Function Test - HYDAC ELECTRONIC HFS 2100 Bedienungsanleitung

Elektromechanischer durchfluss-schalter mit atex-zulassung für öle / viskose medien
Vorschau ausblenden Andere Handbücher für HFS 2100:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Flow switch HFS 2100 with ATEX approval
4.4.4

Electrical connection

The switching contacts used in the instruments are potential free and do not need any supply.
Attention!
Switching contact and unit are matched. After the exchange of a switching contact a
readjustment must be made.
Kindly request the relevant instruction.
Change-over contact SEM-A
2
3
1
Lead no. 1
Common
Lead no. 2
Normally closed
Lead no. 3
Normally open

4.4.5 Function test

The function test must be made outside the Hazardous Area!
Change-over contact (SEM-A):
The function test is performed with a cable tester and a magnet. If measured between core 1 and 2
of the connecting cable, the cable tester must switch from "conductive" to "nonconductive" when
the magnet is in approximation to the front side of the switch unit. If measured between core 1 and
3 of the connecting cable the action of the cable tester must be reversed. The dielectric resistance
(electrical connections – housing) must be > 10 MΩ.
Normally-open contact (SEM-E):
The function test is performed with a cable tester and a magnet. If the magnet is in approximation
of the front side of the switch unit the cable tester must indicate "conductive" when the switch is
triggered.
The dielectric resistance (electrical connections – housing) must be > 10 MΩ.
Status 2020/05/19
Normally open contact SEM-E
Lead no. 1
Lead no. 2
HYDAC ELECTRONIC GMBH
2
1
Common
Normally open
Mat. No.: 669863
Page 8

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis