Herunterladen Inhalt Inhalt Diese Seite drucken

For Stranded Wiring; Examples Of Shield Wires - Panasonic S-36PK1E5A Installationsanleitung

Single split air conditioner
Vorschau ausblenden Andere Handbücher für S-36PK1E5A:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 69
How to connect wiring to the terminal

■ For stranded wiring

(1) Cut the wire end with cutting pliers,
then strip the insulation to expose
the stranded wiring about 10 mm and
tightly twist the wire ends. (Fig. 4-7)
(2) Using a Phillips head screwdriver,
remove the terminal screw(s) on the
terminal board.
(3) Using a ring connector fastener or
pliers, securely clamp each stripped
wire end with a ring pressure terminal.
(4) Place the ring pressure terminal,
and replace and tighten the removed
terminal screw using a screwdriver.
(Fig. 4-8)

■ Examples of shield wires

(1) Remove cable coat not to scratch braided shield. (Fig. 4-9)
(2) Unbraid the braided shield carefully and twist the
unbraided shield wires tightly together. Insulate the shield
wires by covering them with an insulation tube or wrapping
insulation tape around them. (Fig. 4-10)
(3) Remove coat of signal wire. (Fig. 4-11)
(4) Attach ring pressure terminals to the signal wires and the
shield wires insulated in Step (2). (Fig. 4-12)
■ Wiring samples
K1 type
Functional ground screw (External Electronic
Expansion Valve Kit and Schedule Timer)*
Protective ground screw
Fixture screw for resin cover
Resin cover
R1
L1
L2
N
Inter-unit Control Wiring
Power Supply
Use this screw when connecting the shield
for the Inter-unit control wiring to ground.
* As to functional ground screw and protective ground screw,
remove the fixture screw and resin cover. Then, carry out
earth ground work.
Stranded wire
Ring
pressure
terminal
Fig. 4-7
R2
U1
U2
Remote Control Wiring
Special
Screw
washer
Ring pressure
terminal
Terminal board
Wire
Fig. 4-9
Insulation tape
Fig. 4-10
Insulation tape
Fig. 4-11
Fig. 4-12
17
Screw and
Special washer
Ring
pressure
terminal
Wire
Fig. 4-8
Shield mesh
Shield mesh

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis