Herunterladen Inhalt Inhalt Diese Seite drucken

Panasonic WH-SDC03E3E5 Bedienungsanleitung Seite 5

Vorschau ausblenden Andere Handbücher für WH-SDC03E3E5:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 32
SETTING UP THE SPECIAL FUNCTIONS
SETTING UP THE SPECIAL FUNCTIONS
• After initial installation, you can manually adjust the settings. The initial setting remains active until the user changes it.
• The control panel can be used for multiple installations. Some functions may not be applicable to your unit.
• Ensure the operation LED is in OFF condition before setting.
SETTING
STATUS
SET
CHECK
SELECT
CANCEL
Set Control Panel's Display Description
1
2
HEATER
3
4
TANK
5
SOLAR
6
COOL
7
HEAT
8
COOL/HEAT
9
TANK
10
BOOSTER
11
BOOSTER
Do not use the system during sterilization to prevent scalding or overheat during shower.
The sterilization function fi eld settings must be confi gured by the authorized dealer according to local laws and regulation.
12
13
14
15
SET
CHECK
1. Press
and
simultaneously for 5 seconds to enter special setting mode.
"SETTING" and "STATUS" indicator is ON.
2. Press
or
to browse functions.
SELECT
3. Press
to enter function.
or
to enable YES or disable NO function, or set other options.
4. Press
SET
5. Press
to confi rm.
External Thermo Controller (YES / NO)
To set external thermo controller connection.
Indoor Backup Heater Capacity Selection (3kW / 6kW / 9kW)
To reduce the heater power whenever unnecessary. Options vary depending on model.
Water System Freeze Prevention Function (YES / NO)
To activate or deactivate water system freeze prevention function when unit is OFF.
Tank Connection (YES / NO)
To set tank connection.
Note: If select "Tank connection" is "NO", Set 5 ~ 14 are skipped.
Solar Priority (YES / NO)
To choose the solar use for water tank heat up.
Cooling Priority (YES / NO)
To choose the room cooling as priority during COOL + TANK mode.
If select "Cooling priority" is "YES", Set 8 ~ 9 are irrelevant to COOL + TANK mode.
Heating Priority (YES / NO)
To choose the room heating as priority during HEAT + TANK mode.
Note: If select "Heating priority" is "YES", Set 8 ~ 9 are irrelevant to HEAT + TANK mode.
Cooling/Heating operation Interval Set
To set timer for Cool mode or Heat mode during COOL + TANK mode or HEAT + TANK mode
(0.5hour ~ 10 hours). If both "Heating priority" and "Cooling priority" are "YES", Set 8 ~9 are skipped.
Tank Heat-up Interval Set
To set timer for Tank during COOL + TANK mode or HEAT + TANK mode
(5minutes ~ 1hour 35minutes).
Booster Heater Function (YES / NO)
To activate or deactivate tank booster heater function
Note: If select "Booster heater function" is "NO", Set 11 is skipped.
Booster Heater Delay Timer Set
To set delay timer for booster heater to ON if water tank temperature is not reached
(20minutes ~ 1hour 35minutes).
Sterilization (YES / NO)
To set sterilization, if required.
Note: If select "Sterilization" is "NO", set 13 ~ 15 are skipped.
Sterilization Day & Time Set
To set timer for sterilization (only once a week, will operate even in standby condition).
Sterilization Temperature Set
To set temperature for sterilization function (40°C ~ 75°C).
Sterilization Continue Time
To set timer to maintain heating temperature in order to complete the sterilization
function (5minutes ~ 1hour).
5

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Wh-ud03ee5Wh-sdc05e3e5Wh-ud05ee5

Inhaltsverzeichnis