Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - Baxi Power HT 1.450 Gebrauchsanleitung

Für den verbraucher und den installateur
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Boiler model POWER HT
Category
Maximum heat input
Minimum heat input (G20)
Minimum heat input (G31)
Maximum heat output 75/60°C
Maximum heat output 50/30°C
Minimum heat output 75/60°C (G20)
Minimum heat output 75/60°C (G31)
Minimum heat output 50/30°C (G20)
Minimum heat output 50/30°C (G31)
Useful efficiency according to 92/42/CEE directive
Central heating system max. pressure
Heating circuit temperature range
Type
Flue duct diameter
Max. flue mass flow rate
Min. flue mass flow rate
Max. flue temperature
NOx class
Type of gas used
Natural gas feeding pressure 2H
Propane gas feeding pressure 3P
Power supply voltage
Power supply frequency
Rated power supply
Net weight
Dimensions
*C53 (only with air intake kit)
Ed. 2 - 06/14

23. TECHNICAL DATA

BAXI S.p.A.
36061 BASSANO DEL GRAPPA (VI) ITALIA
Via Trozzetti, 20
Servizio clienti: Tel. 0424 - 517800 - Telefax 0424/38089
www.baxi.it
kW
kW
kW
kW
kcal/h
kW
kcal/h
kW
kcal/h
kW
kcal/h
kW
kcal/h
kW
kcal/h
bar
°C
mm
kg/s
kg/s
°C
mbar
mbar
V
Hz
W
kg
height
mm
width
mm
depth
mm
1.450
1.650
II
II
2H3P
2H3P
46,4
67
12,2
13,8
12,2
19,9
45
65
38700
55900
48,7
70,3
41882
60458
11,8
13,4
10148
11524
11,8
19,3
10148
16598
12,8
14,5
11008
12470
12,8
20,9
11008
17974
4
4
25÷80
25÷80
B23 - B23P - C53 *
80
80
0,022
0,031
0,006
0,007
72
73
5
5
G20
G20
G31
G31
20
20
37
37
230
230
50
50
90
110
60
68
850
850
450
450
621
693
Cod. 7115306.01

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Power ht 1.650

Inhaltsverzeichnis