DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10  minutes,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing. The
voltage MUST be less than 50 V DC before you can touch
electrical components. For the location of the terminals,
see the wiring diagram.
g
f
DC P1+
DC N1-
e
d
c
b
a
a
Multimeter (DC voltage range)
b
S80 – reversing solenoid valve lead wire
c
S20 – electronic expansion valve lead wire
d
S40 – thermal overload relay lead wire
e
S90 – thermistor lead wire
f
LED
g
S70 – fan motor lead wire
7.1
Specifications of standard wiring
components
Component
Power supply
Voltage
cable
Phase
Frequency
Wire sizes
H05RN-F (60245 IEC 57)
Interconnection cable
(indoor↔outdoor)
1.5 mm
H05RN-F (60245 IEC 57)
Recommended circuit breaker
Earth leakage circuit breaker
MUST comply with applicable
(a)
Electrical equipment complying with EN/IEC 61000-3-12
(European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public
low-voltage systems with input current >16 A and ≤75 A per
phase).
7.2
To connect the electrical wiring to
the outdoor unit
1 Remove the service cover.
2 Remove the switch box cover.
3 Open the wire clamp.
4 Connect the interconnection cable and power supply as follows:
RXF50~71D5V1B
R32 split series
3P645642-2E – 2021.10
5 Tighten the terminal screws securely. We recommend using a
220~240 V
6 Install the service cover.
1~
7 Install the switch box cover.
50 Hz
8
3-core cable
2
2.5 mm2~4.0 mm
8.1
4-core cable
2
2
~2.5 mm
and applicable for
220~240 V
(a)
20 A
legislation
1 Insulate and fix the refrigerant piping and cables as follows:
a
b
g
2 Install the service cover.

8 Finishing the outdoor unit installation

a
b
a
Interconnection cable
b
Power supply cable
c
Circuit breaker
d
Residual current device
e
Power supply
f
Earth
1 2 3
Phillips screwdriver.
Finishing the outdoor unit
installation
To finish the outdoor unit
installation
DANGER: RISK OF ELECTROCUTION
▪ Make sure that the system is earthed properly.
▪ Turn OFF the power supply before servicing.
▪ Install the switch box cover before turning ON the
power supply.
d
c
e
f
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Field wiring (if applicable)
e
Liquid pipe
f
Liquid pipe insulation
g
Finishing tape
50 Hz
c
d
220-240 V
e
f
Installation manual
11