Herunterladen Inhalt Inhalt Diese Seite drucken

GOK HS-V.2 Montage- Und Bedienungsanleitung Seite 23

Membrangesteuerte hebersicherung
Vorschau ausblenden Andere Handbücher für HS-V.2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Figure 3: Vacuum test kit UPE 300
Recommendation
GOK Vacuum test kit UPE 300 (Part-No.13 602 00) with vacuum pump
(Part-No.13 610 89):
• Test vacuum -300mbar.
• Test the complete supply system from the tank withdrawal fitting to the burner for leaks.
Possible before start-up.
The anti-siphon device can be included in the pressure and leak tests if it is set to "ventilate"
- see OPERATION.
• Observe the consuming appliance manufacturer's instructions for start-up.
• The time required for starting up the supply system can be reduced by ventilating the anti-
siphon device. The handwheel must be set to the safety height HA and be sealed so that it
cannot be adjusted without authorisation.
Operating safety: Adjust HA so that the actual height difference ∆X is just
safeguarded. Definition: HA ≥ ∆X
Higher HA values lead to greater opening pressures p
vacuums in the suction line and increased formation of gas bubbles.
1. Measure the height difference ∆X between the installation position of the anti-siphon
device and the lowest point of the suction line – generally, the hose on the floor in front of
the point of consumption.
The setting for the safety heightaccording to Points 2 and 3 applies for fuels with a
maximum density of ≤ 860kg/m³, e.g., fuel oil EL. Otherwise, point 4. page 9 applies.
2. Set the correct safety height HA from the measured height difference ∆X:
Type
Height setting HA in
HS-V.2
Artikel-Nr. 15 513 50 c
:
p
[m]
0.5
1.0
2.0
3.0
4.0
and, consequently, to higher
o,o
in [mbar]
o,o
-75
-115
-200
-284
-366
Pressure loss ∆pv at V in [mbar]
40l/h
-
< 5
< 10
< 10
< 10
220l/h
-
40
47
52
60
23 / 60

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für GOK HS-V.2

Inhaltsverzeichnis