1
Installation
Enables the connection of the following fire service equipment:
–
–
–
–
–
Notice!
The programming has to be in line with the guidelines and requirements of your local fire
brigade.
Notice!
For the correct connection to an AT 5000 transmission unit, refer to the latest version of the
Wiring Guide.
Position Terminal
1
2
3
4
5
6
7/8
9
10
11
12
13
14
15
16
17/18
19/20
21-32
Bosch Sicherheitssysteme GmbH
Transmission unit to fire service
Key deposit
Signaling light for key deposit
Monitoring of a release device
4 programmable relays
Connection
A
Ground
B
Transmission unit control
C
Checkback signal
ÜE
Fault AWUG
NQuit
Acknowledge
GND
Ground
ÜE+/ÜE-
Transmission unit power supply
1
Monitoring of key deposit
Jumper from position 10 to 11 for magnetic door release of 12 V key
deposit
2
Ground
5
Magnetic door release, 24 V, approx. 10 W
8
Monitoring door lock
6/7
Ground
9
Heating, 24 V, approx. 8 W
10
Ground
FSE +/-
Monitoring release device
+/-
Signalling light, 24 v, approx. 10 W
1 / 2 / 3 / 4 Relays NO (normally open), C (common), NC (normally closed)
Installation Manual
Installation | en
7
05.2020 | 2.0 | F.01U.063.946