Selecting the operating mode
®
DIP switch 10 can be used to specify whether RN221N with HART
diagno-
®
sis evaluates the HART
status bytes or the E+H diagnostic command #231.
If all the DIP switches from 4-9 are in the "OFF" position (no masking of a sta-
tus bit or a stage in the "quality code"), the 4-20 mA signal is automatically
used for failure signal detection regardless of which position DIP switch 10 is
set to.
Bypassing the internal 250  communication resistor
The internal communication resistor can be bypassed using DIP switch 1 to
make it possible to use an external communication resistor. It is then no longer
®
possible to connect a HART
master to the communication jacks of RN221N.
Primary/secondary master
DIP switch 3 can be used to specify whether RN221N polls the transmitter as
®
a primary or secondary master. This setting is important if another HART
master, apart from RN221N, is in the network (e.g. control system with
®
HART
functionality). This setting must be selected in such a way that there
®
®
are never two HART
masters of the same type in the HART
network. This
setting is not significant in the "Current measurement" operating mode.
37