06.2006
11
Technical Data
EC Low-Voltage Directive
73/23/EEC and RL93/68/EEC
EC EMC Directive 89/336/EWG
EC Machinery Safety Directive
89/392/EEC
Approvals
Type of cooling
Permissible ambient or coolant
temperature
•
During operation
•
During storage
•
During transport
Installation altitude
Permissible humidity rating
Environmental conditions
to DIN IEC 721-3-3
Pollution degree
Overvoltage category
Type of protection
Protection class
Shock-hazard protection
Radio interference level
•
Standard
•
Options
Noise immunity
Paint
Miscellaneous
Siemens AG
6SE7087-6KP50
SIMOVERT MASTERDRIVES
EN 50178
EN 61800-3
EN 60204-1
UL:
E 145 153
CSA:
LR 21 927
cULus: E 214113 (
Air-cooled with installed fan
0° C to +45° C ( 32° F to 113° F)
(to 50° C, see fig. "Derating curves")
-25° C to +55° C (-13° F to 131° F)
-25° C to +70° C (-13° F to 158° F)
≤ 1000 m above sea level (100 per cent loadability)
> 1000 m to 4000 m above sea level
(Loadability: see fig. "Derating curves")
Relative air humidity
Climate:
Chemically active substances: 3C1
Pollution degree 2 to IEC 664-1 (DIN VDE 0110, Part 1),
Moisture condensation during operation is not permissible
Category III to IEC 664-1 (DIN VDE 0110, Part 2)
IP20 EN 60529
Class 1 to EN 536 (DIN VDE 0106, Part 1)
EN 60204-1 and to DIN VDE 0106 Part 100 (BGV A2)
According to EN 61800-3
No radio interference suppression
Radio interference suppression filter for class A1 to EN 55011
Industrial sector to EN 61800-3
Indoor duty
The devices are ground-fault protected, short-circuit-proof and idling-
proof on the motor side
Operating Instructions
≥
22 kW)
≤ 95 % during transport and storage
≤ 85 % in operation (condensation not
permissible)
3K3
Technical Data
11-1