MALFUNCTIONS AND TROUBLESHOOTING
DANGER
The device contains parts under life-threateningly high electrical voltage.
– Have all repair work performed by specialists.
– Never operate the distribution box if it is defective.
– Electrical loads which are connected to the distribution box may start automatically when triggered
protective equipment is re-activated and cause injuries.
– Only activate protective equipment when you have switched off all connected loads or disconnected them
from the distribution box.
If one of the connected loads is no longer supplied with voltage, proceed as follows:
1. Pull the corresponding plug out of the distribution box.
2. Check the distribution box and the connected loads for defects in a visual inspection.
– If one of the devices is defective, inform a qualified electrician.
Troubleshooting is hereby completed.
– If this is not the case, proceed with step 3.
3. If applicable, check whether the fuse or the residual current device have been triggered. If this is the case,
proceed with step 4; otherwise inform a qualified electrician.
Troubleshooting is hereby completed.
4. Open the housing cover, fig. B (9).
5. Switch on the fuse fig. B (5) or the residual current device fig. B (4).
6. If the fuse is triggered again, the distribution box is faulty.
Proceed with step 7.
If the fuse is not triggered, proceed with step 9.
7. Close over the housing cover.
8. Decommission the distribution box and inform an electrician or the service department of the manufacturer
immediately.
Troubleshooting is hereby completed.
9. Re-plug load. If the fuse is triggered again, the load or its supply cable is faulty.
10. Close over the housing cover.
11. Inform an electrician. Troubleshooting is hereby completed.