Herunterladen Diese Seite drucken

S+S REGELTECHNIK THERMASGARD Serie Konfigurationsanleitung Seite 23

Ethercatp-fähige messumformer für temperatur, feuchte, druck und volumenstrom

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

  • DEUTSCH, seite 3
G
EtherCAT P | Configuration (general)
MODULE BAR GRAPH ( SDO )
Object
DataType
0x70n0
REAL
0x70n1
REAL
REAL
0x70n2
REAL
REAL
0x80n0
USINT
0x80n1
USINT
0x80n2
BIT3
BIT3
BIT3
0x80n3
USINT
USINT
USINT
USINT
USINT
USINT
USINT
USINT
USINT
0x90n0
STRING (20)
‚n' = dependent on module sequence
Description of MODULE BAR GRAPH
The central control element is the Bar Graph Programming ( 0x80n0 ) bit, which controls the free configuration of the bar-graph
display. If this bit is set to ON, the RxPDOs (equivalent to the objects 0x70n0...0x70n2) are used to activate the bar-graph
display in colour depending on the preselected limits and the bar graph display value Bar Graph Value ( 0x70n0 ) .
In this case, a distinction is made between the three display areas OK level (green) for the operating range, WARN level (yellow)
for the limit range and ERR level (red) for the error range. To shift the display limits dynamically during operation, they were
also incorporated into the process data.
The limits for the colour change and the dynamic brightness control are set using the four configuration registers
Warning Level Min ( 0x70n1 ) , Warning Level Max ( 0x70n1 ) , Error Level Min ( 0x70n2 ) and Error Level Max ( 0x70n2 ) .
In this case, a distinction must be made between a BI- and UNI-directional display, which is specified by the configuration
register Display Mode ( 0x80n1 ) . The BI-directional display shows a central bar graph that extends in both directions while the
UNI-directional bar graph shows an extension from left to right.
Name
Bargraph Value
Bargraph Warning Level
Warning Minimum
Warning Maximum
Bargraph Error Level
Error Minimum
Error Maximum
Bargraph Programming
Bargraph Display Mode
Bargraph Color Setting
OK Level
WARNING Level
ERROR Level
Bargraph Color Register
OK Red
OK Green
OK Blue
WARNING Red
WARNING Green
WARNING Blue
ERROR Red
ERROR Green
ERROR Blue
Bargraph description
Description
Current display value (specification)
Bar graph WARNING area
Minimum range value (BI & UNI)
Maximum range value (BI & UNI)
Bar graph ERROR area
Minimum range value (BI & UNI)
Maximum range value (BI & UNI)
0: Display according to measured value selection
1: Display individually programmable
Bar graph display mode
0: OK-OK-OK-OK-OK-OK-OK (UNI)
1: OK-OK-OK-OK-OK-WRN-ERR (UNI)
2: OK-OK-OK-WRN-WRN-ERR-ERR (UNI)
3: OK-OK-WRN-WRN-WRN-ERR-ERR (UNI)
4: ERR-WRN-OK-OK-OK-WRN-ERR (BI)
5: ERR-WRN-WRN-OK-WRN-WRN-ERR (BI)
6: OK-ERR (colour gradient UNI)
7: WRN-OK-ERR (colour gradient BI)
0: White
1: Yellow
2: Orange
3: Red
4: Violet
5: Blue
6: Green
7: Colour register
dito
dito
RGB (0-255)
Colour register OK level
Colour register WARNING level
Colour register ERROR level
'Device Bar Graph' information text
23
SDO
SDO
SDO
SDO
SDO
SDO
SDO
SDO
SDO

Werbung

loading

Diese Anleitung auch für:

Hygrasgard seriePremasgard serie