Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - S+S REGELTECHNIK AERASGARD RFTF-CO2 Bedienungs- Und Montageanleitung

Vorschau ausblenden Andere Handbücher für AERASGARD RFTF-CO2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

G
®
AERASGARD
RFTF - CO
The maintenance-free microprocessor-controlled AERASGARD
is used to detect the CO
content in air within a range of 0 ppm to 2000 ppm CO
2
The measurement signals from the CO
signals of 0 -10 V. Optionally, this CO
switching output.
Elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment for
installation on vertically or horizontally installed in-wall flush boxes, with predeter-
mined breaking point for on-wall cable entry, or in enclosures made of stainless steel
(top and bottom part are of stainless steel, the lid is screwed on), vandalism-secure
version e.g. for schools, military barracks, and public buildings.
The CO
content of air is determined by a dual beam NDIR sensor (non-dispersive
2
infrared technology). The detection range of this CO
ard applications such as monitoring of residential rooms or conference rooms. Room
ventilation on an as-needed basis, improvement of well-being and customer benefit,
increased comfort as well as a reduction of operating costs by energy conservation
are only some of the beneficial results of employing AERASGARD

TECHNICAL DATA:

Power supply: ........................ 24 V AC ⁄ DC
CARBON DIOXIDE (CO
)
2
CO
sensor: ........................... optical, dual beam sensor (NDIR),
2
Measuring range, CO
:............. 0 ... 2000 ppm
2
Output CO
: ........................... 0 -10 V
2
Measuring accuracy CO
: ......... ± 70 ppm plus 5 % of measured value
2
Pressure dependence: ............. ± 1.6 % ⁄ kPa (referred to standard pressure)
Long-term stability:................. ± 1 % of final value per year
Gas exchange: ........................ by diffusion
TEMPERATURE
Measuring range, temperature: .... 0 ... +50 °C (RTM - CO
Output, temperature: .............. 0 -10 V
Deviation, temperature: ........... ± 0.8 K at +20 °C
HUMIDITY
Measuring range, humidity: ....... 30 ... 80 % r.H.
Output, humidity: .................... 0 -10 V
Deviation, humidity: ................. ± 3 % r. H. at +20 °C, otherwise ± 5 % r. H.
Long-term stability:................. ± 1 % per year
Warm-up time: ....................... ca. 1 hour
Ambient temperature: ............. 0 ...+50 °C
Electrical connection: .............. 0.14 - 1.5 mm
Enclosure: ............................. plastic, material ABS, colour pure white (similar RAL 9010),
Dimensions: ........................... 98 x 106 x 32 mm (Frija II)
Installation: ........................... wall mounting or on in-wall flush box, Ø 55 mm, base with 4-hole
Protection class: .................... III (according to EN 60 730)
Protection type: ..................... IP 30 (according to EN 60 529)
Standards: ............................ CE-conformity, electromagnetic compatibility
⁄ RTM - CO
2
2
®
RFTF-CO
transmitter are converted into standard
2
measuring transducer can be supplied with
2
sensor is calibrated for stand-
2
with automatic self-calibration,
non-dispersive infrared technology,
dual beam measuring method
At the RFTF - CO
the measuring range
2
is selected via two switching thresholds,
which are set at two potentiometers:
Lower limit via S1 (0 V), upper limit via S2.
At the RTM - CO
- 2S the operating mode
2
can be changed via pushbutton:
Automatic, Manual (Step 1 and Step 2), and OFF.
⁄ RTM - CO
2
+5 ... 40 °C (RFTF - CO
⁄ RTM - CO
2
(RFTF - CO
)
2
2
, via terminals on circuit board
stainless steel enclosure optional
100 x 100 x 25 mm (stainless steel enclosure)
for mounting on vertically or horizontally installed in-wall flush boxes
for cable entry from the back, with predetermined breaking point
for on-wall cable entry from top ⁄ bottom in case of plain on-wall installation
according to EN 61 326 + A1 + A2, EMC directive 2004 ⁄ 108 ⁄ EC,
low-voltage directive 73 ⁄ 23 ⁄ EEC
⁄ RTM - CO
2
2
Connecting diagram
.
2
®
CO
sensors.
Connecting diagram
2
Connecting diagram
- A)
2
- 2S)
2
UB+ 24V AC/DC
1
2
UB- GND
3
GND
4
Output 0-10V humidity in % r.H.
5
GND
6
Output 0-10V temperature in °C
7
GND
Output 0-10V CO
content in ppm
8
2
1
UB+ 24V AC/DC
2
UB- 24V AC/DC
3
Free
4
Free
5
GND
6
Free
7
Free
Output CO
content in ppm 0-10V
8
2
9
Output temperature in °C 0-10V
1
UB+ 24V AC/DC
2
UB- GND
3
Free
4
Free
5
GND
6
Output 0-10 V temperature in °C
7
GND
Output 0-10 V CO
content in ppm
8
2
9
Step 2 (normally open contact) 5A/250V~
10
Step 2 (normally open contact) 5A/250V~
11
Step 1 (normally open contact) 5A/250V~
12
Step 1 (normally open contact) 5A/250V~
RFTF - CO
2
RTM - CO
2
RTM - CO
- A
2
RTM - CO
- 2S
2

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis