6

Operation

For safety reasons, liquid must escape via the discharge line of the safety
valve during heating.
 Verify that the safety valve is not shut off.
1. If the safety valve has responded, check the system.
2. Remove the cause before recommissioning the system.
3. Perform a function test of the safety valve (see chapter "Function test
safety valve").
7

Maintenance

7.1
Maintenance intervals
When
Every 6 months
7.2
Maintenance activity
HOT LIQUID
Water in heating systems can have temperatures of more than 100 °C.
Verify that blown off liquid cannot cause injury or damage.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
Replacing the quick air vent
Due to the integrated mounting valve, the quick air vent can be replaced while
the system is under pressure.
Operation
Activity
Perform a function test of the safety valve (see
chapter "Function test safety valve").
WARNING
KSG mini
EN
12