UNITS INSTALLATION
10.2. FAN PERFORMANCE CURVE
Outdoor unit could be installed using ducts at inlet and outlet air.
Refer to fan performance curve, in order to ensure that the air volume is within working range.
It's assumed that unit will be installed using supply and return air ducts. Find below fan performance curve to decide which ducts
are suitable
NOTE:
When design a duct, check to ensure that the Air volume is within working range as indicate "Fan Performance Curve".
-
If the Air volume is set outside working range, water-carry-over (drop in the ceiling or into the room), noise increases, fan motor
-
damaged (high temperature), insufficient Cooling/Heating capacity, phenomena can occur.
Therefore design ducts and select the correct fan speed in order to keep the unit running in the accepted working range
-
selected.
Specific installation comment for RASC-5HNE:
•
-
It's recommended to set up ducting work in order to keep static pressure around 10mmAq. If measuring static pressure or
airflow is not available, measuring ampers can give and idea of working point. As a reference, at Pst = 0mmAq is 5.4 A, and at
Pst = 10mmAq is 4.65 A approximately (only approximated since motor temperature, voltage will affect Amps measurement).
If installation requires short and straight ducts (Pst ≤3mm Aq) installation, whistle air sound could appear. in order to avoid this
-
situation it's advisable to close suction air inlet on outdoor unit (half of suction air inlet closed, for example).
Downloaded from
www.Manualslib.com
RASC-5HNE
Air flow (m³/min)
Nominal Point
manuals search engine
RASC-10HNE
Air flow (m³/min)
Nominal Point
PMGB0126A rev.2 - 11/2006
14