Herunterladen Inhalt Inhalt Diese Seite drucken

Dräger Polytron Repeater Isa; Sensors; Interfaces; Intended Use - Dräger Polytron 6100 EC WL Gebrauchsanweisung

Vorschau ausblenden Andere Handbücher für Polytron 6100 EC WL:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Contact the Dräger sales team to purchase the Dräger
PolySoft configuration software.

Operation

A ISA100 Wireless
process interface communicates the gas
reading, measurement status (PV.STATUS), and device
status (DIAG_STATUS) to the controller.
Alarms
The alarms configured in the gas detector are not transmitted
via the ISA100 Wireless
output via the red LED and are not used to trigger
countermeasures. The alarms are non-latching. When alarm
conditions are resolved, the alarm is no longer displayed.
If alarm logic is used for countermeasures, implement alarm
logic in the controller.
Maintenance
In potentially explosive gas atmospheres, the gas detector
can be serviced without declassifying the area.
In areas at risk of dust explosion, the area must be
declassified beforehand.
3.2.2 Dräger Polytron Repeater ISA
The Dräger Polytron Repeater ISA is a version of the Dräger
Polytron 6100 EC WL without measuring function.
3.3

Sensors

The gas detector is intended for use with the DrägerSensor
EC (electrochemical). Select the sensor according to the
target gas to be measured.
3.4

Interfaces

Interface
ISA100 Wireless
net-
work
®
Bluetooth
3.5

Intended use

3.5.1 Dräger Polytron 6100 EC WL
The gas detector is used in conjunction with the built-in
DrägerSensor for monitoring toxic gases and oxygen.
3.5.2 Dräger Polytron Repeater ISA
The repeater is used to increase the range of the radio signal.
Dräger Polytron 6100 EC WL, Dräger Polytron Repeater ISA
process interface. Alarms are only
Connection via the network (see
"Network integration", page 26).
Connection to a Windows mobile
device in the field (see "Activat-
®
ing the Bluetooth
interface",
page 23).
3.6

Approvals

The approvals are shown on the name plate. A copy of the
name plate and the declaration of conformity can be found in
the document "Notes on Approval" (order no. 93 00 060).
4
Operation
If the product is operated by a battery, do not remove the
battery box during configuration.
4.1

LED display

Symbol LED display
Green LED
flashes once
Yellow LED
flashes once
Yellow LED
lights up con-
tinuously
Red LED
flashes once
Red LED
flashes twice
Blue LED
flashes once
Blue LED
lights up con-
tinuously
Yellow and
blue LEDs
light up
When the LED display is active, the energy consumption
increases.
4.2

Communication interfaces

®
4.2.1 Bluetooth
interface
After the start sequence, the Bluetooth
automatically activated. If no connection is established, the
gas detector disables the interface after 10 minutes (factory
setting).
4.2.2 Activating the Bluetooth
®
● Activate the Bluetooth
via the ISA100 Wireless
● Magnetic pen: Tap the marking (Fig. A 11).
Operation
Meaning
Gas detector is switched on
Warning (e.g., battery charge state
low or sensor warm-up phase
active)
Error
A1 alarm (pre-alarm)
A2 alarm (main alarm)
®
Bluetooth
active
®
Bluetooth
active, connected to
Windows mobile device
Confirmation, internal battery
counter reset
®
interface is
®
interface
interface with a magnetic pen or
network:
en

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Polytron repeater isa

Inhaltsverzeichnis