Installation Instructions
General instructions
Preparation
Fire Safety
Installation
Repairs
Technical details Solea
General instructions
The Solea is tested in accordance with the international
EN 13240 standardization, and has an extra additional
standardization for optimally environment-friendly
heating devices related to flue gases (Section 15a B-Vg.
Des BmfWA). The stove can be connected to a flue
tube to which several stoves are connected. The Solea
should never been integrated into the construction of the
room.
The heating device must be placed by an acknowledged
installer and according to the installation instructions
given below. The national and local rules and regulations
for placing and using wood-burning stoves are equally
applicable. WANDERS does not give any guarantee
if the stove is connected or installed incompletely or
incorrectly.
It is not allowed to place the stove in:
• Arcades and corridors accessible to the public.
• Stairwells, except in buildings with no more than 2
dwellings.
• Spaces where highly flammable or explosive materials
are used.
• Spaces where an exhaust system is used or where a
mechanical exhaust system is placed, except when
the air supply is taken directly from outside to assure
a hazardless combustion.
Preparation
The chimney flue
Before placing the stove you must observe the following
points:
• If the stove is connected to an existing chimney, you
must first have the chimney professionally cleaned
and checked by a qualified chimney sweep company.
Any cut-off valves or stop valves must be removed.
• The flue tube of the stove must be connected with the
chimney without diversions.
19
19
19
20
20
21
• The underpressure in the chimney must be at least 12
Pa or 0.12 mbar.
• The chimney flue must always end up in outlet area 1
(see the drawing below)
Roof slope x larger than 23°
• At the time of placing the stove, the chimney flue
must be clean, leak-proof and without obstructions,
and must have a diameter of 150 mm.
• Any bends in the flue tube must not exceed 45
degrees.
• Ensure that the chimney tube can discharge the flue
gases adequately, properly and safely.
• The values for calculating the chimney tube is given
in the section on Technical Information, see above.
Fire Safety
For reasons of fire safety is it important to observe the
instructions below before installing the stove.
1.
The free distance from the fire-proof rear wall is at
least 10 cm in each rotated position.
2.
Keep at least a distance of 80 cm between the stove
and combustible objects such as curtains, wooden
objects (cupboards and paintings) and glass objects.
Keep the same distance from the flue tube.
3.
Wooden construction parts within the radiation
range of the stove (80 cm from the exterior of the
stove) must be covered with fireproof material.
Roof slope x smaller than 23°
19