6. Commissioning, operation
lation, instruments with liquid filling should be used. The instruments
should be protected against coarse dirt and wide fluctuations in ambient
temperature.
WARNING!
Physical injuries and damage to property and the
environment caused by the back blowing out in the
event of a failure
Due to the high energy in the back, if it is blown out in the
event of a failure, there is a risk of physical injuries or damage
to property through the ejected back and the media that
would then escape.
It must be ensured that at no time can personnel or objects
be at the rear of the instrument.

6.3 Installation

Depending on the application, the instrument should be filled with the
medium before screwing in, in order to ensure it functions properly.
Nominal position per EN 837-1 / 9.6.7 image 9: 90°±5° ( ⊥ ), if not
stated otherwise in the order documentation.
Process connection lower mount or back mount
After installation, open the vent valve (if available) or set from CLOSE
to OPEN. The version of the vent valve depends on
the model and can deviate from the illustration!
For outdoor applications, the selected installation
location has to be suitable for the specified ingress protection, so
that the pressure gauge is not exposed to impermissible weather
conditions.
Operating instructions capsule pressure gauge, model 63x.50 per ATEX
EN
21