Technical data
EU Type Examination Certificate
Type group
Marking gas Ex
Marking dust Ex
Maximum value Ui
Maximum value Ii
Maximum value Pi
Effective internal capacity Ci
Effective internal inductivity Li
Temperature range in T6 (zone 0 or 1)
Temperature range in T5 (zone 0 or 1)
Temperature range in T4 (zone 0 or 1)
Temperature range in T3 (zone 0 or 1)
Temperature range dust Ex (zone 20)
Maximum surface temperature (zone 20)
Detection range water
Detection range oil
Detection range air
Stand-by time before availability
Switch-on delay
Switch-off delay
Material of sensor housing/flange
Permissible process pressure for the equipment in an
explosive atmosphere
Compressive strength of the sensor tip
Test voltage
Degree of protection [EN 60529]
Electrical connection
Accessories
Hans Turck GmbH & Co. KG | Witzlebenstraße 7 | 45472 Mülheim an der Ruhr | Germany | T +49 208 4952-0 | www.turck.com
TÜV 99 ATEX 1517 X
1
` II 1 G Ex ia IIC T6...T3 Ga
` II 1/2 G Ex ia IIC T6...T3 Ga/Gb
` II 1 D Ex ia IIIC T125 °C Da
13,65 V
200 mA
690 mW
0,27 nF
1,3 µH
-20 °C ≤ Ta ≤ +40 °C
-20 °C ≤ Ta ≤ +55 °C
-20 °C ≤ Ta ≤ +85 °C
-20 °C ≤ Ta ≤ +85 °C
-20 °C ≤ Ta ≤ +85 °C
125 °C
1...100 cm/s
3...200 cm/s
-
typ. 8 (2...18) s
typ. 2 (1...13) s
typ. 2 (1...13) s
1.4571/AISI 316 Ti / - (3.1 acc. to DIN EN 10204:2005)
0.8 ... 1.1 bar absolute
60 bar / 870 psi
500 V AC / 50 Hz / 60 s
IP 67
2 m PVC cable blue, 4 x 0,75 mm²
2 x gasket AFM 34 G3/4
2