Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data; En Conformity; Accessories - Honeywell 010128 Montage, Anschluss, Anleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

20
Mounting and Connection Instructions 2 Detector group module BUS-2/BUS-1, f.m.
11.

Technical data

Rated operating voltage
Operating voltage range
Current consumption at U_b=12 V DC:
- Detector groups open
- Detector groups terminatd with 12k1
- LED indicator
- when cleared
2 detector group inputs with clear function
- Voltage
1)
- Monitoring range
Protection class as per EN 60529
Environmental class as per VdS
Environmental class as per EN 50131-1
Operating temperature range
Storage temperature range
Relative humidity
Installation
Dimensions:
- Mounting dimensions (Æ x D)
- Mounting frame (W x H x D)
- Cover frame (W x H x D)
- 2-module cover frame (W x H x D)
Weight
Colour
1)
Depending on the control panel and the operating mode of the module, the monitoring range
is programmable (see 5.3)
12.

EN Conformity

Module Item no. 010128 as per EN 50131-3, Security grade 2, Environmental Class II
13.

Accessories

010124.17
Decorating foil (PU = 5 pce.)
Honeywell Security Group
Novar GmbH
Johannes-Mauthe-Straße 14
D-72458 Albstadt
www.honeywell.com/security/de
12 V DC
9 V to 15 V DC
£ 3.5 mA
£ 0.6 mA in addition per detector group
£ 1.3 mA in addition per LED
no additional current consumption
8 V DC, stabilized, short-circuit protected
12k1 ± 20%
IP 40
II
Class II
-10 °C to +55 °C
-25 °C to +70 °C
max. 93% non-condensing
Suitable for installating in flush mounted box with
Æ 60 mm (DIN, Austrian or Swiss)
58 x 26 mm
70 x 70 x 1 mm
80 x 80 x 5 mm
151 x 80 x 5 mm
37 g
traffic white (similar to RAL 9016)
P00175-10-002-06
2015-03-05
© 2015 Novar GmbH

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis