IMPORTANT: * These values are for information only, they should be checked and selected to comply with the local and/or
national codes and regulations. They are also subjected to the type of installation and size of conductors.
** The appropriate voltage range should be checked with data label on the unit.
Heat Pump
FDMY(P) 75/100D
Fuse /
Main
Circuit
Switch
Breaker
R / L1
S / L2
T / L3
Power
N
Supply
!
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
Model
Voltage range**
Power supply cable size* / mm²
A) Indoor
B) Outdoor
C) Total
Number of conductors
A) Indoor
B) Outdoor
Interconnection cable size* / mm²
Number of conductors
Recommended fuse/circuit breaker* / A
A) Indoor
B) Outdoor
C) Total

ELECTRICAL CONNECTION

R
S
T
Power
Supply
Cable
Indoor
Outdoor
Indoor
Outdoor
N
OF
L
4WV
COMP
A
OF
L
4WV
COMP
FDMY(P) 75D
RCY(P) 75E(G)
220-240V/1PH/50Hz+ !
380-415V/3PH/50Hz+ !
1
2.5
2.5
-
5
1
7
10
25
32
1-12
N
N
LP HP DS DS
To Indoor Control Board
Indoor Unit
N
Terminal Block
FDMY(P) 100D
RCY(P) 100E(G)
12
40
40
Outdoor Unit
Terminal Block
1
4
4
-
5
1
7