Compatible spare for IS1 I/O modules:
Series 9460/12*), 9461/12 *), 9465/12 and 9466/12
*) for operation with active 4-wire HART transmitters, a 9164 is additionally required for
each channel
6
Components
6.1 Overview
1
2
3
4
5
6.2 Pluggable terminal X1
For the module, a pluggable terminal X1 (screw-type terminal 162702 or
spring clamp terminal 162695) for connection of field devices is available as accessory
(not included in the scope of delivery of the module!).
The pluggable terminal X1 has 16 terminals for connection of the field cables.
X1
1
2
3
4
5
6
4 ... 20 mA HART
Terminal assignment
X1
2-wire input/output with HART
Channel
Terminals
0
1(+), 2(-)
1
3(+), 4(-)
2
5(+), 6(-)
3
7(+), 8(-)
4
9(+), 10(-)
5
11(+), 12(-)
6
13(+), 14(-)
7
15(+), 16(-)
The channels have no common connection to earth among themselves.
218080 / 946860310020
2015-10-30·BA00·III·en·02
1
Operating flap with insert label (open) and connection diagram
2
Module data (serial number, hardware revision number, software revision number,
manufacturing date, e.g.: 123456DE9999 Rev.A 01-01 0508)
3
Notch lever for removing the module from the BusRail
LED for operation indication ("RUN", green), error ("ERR", red) and maintenance
4
("M/S", blue) (for further information, see "LED indications and troubleshooting")
5
Pluggable terminal X1 with two safety screws
15323E00
7
8
9 10 11 12 13 14 15 16
X1
3-wire input with HART
Terminals
supply 1(+), signal 2(+), common 4(-)
--
supply 5(+), signal 6(+), common 8(-)
--
supply 9(+), signal 10(+), common 12(-)
--
supply 13(+), signal 14(+), common 16(-)
--
NOTICE
Analog Universal Module
HART for Zone 2
9468/33
Components
15324E00
X1
4-wire input
Terminals
2(+), 4(-)
--
6(+), 8(-)
--
10(+), 12(-)
--
14(+), 16(-)
--
5