People Counter RAZL-2CO (Translation)
2.13 Description of the configurations
Current number of persons
Maximum number of persons
allowed
Alarm when the permitted
number of persons is
exceeded
Installation location of the
counting light barrier (sensor
pillar)
Error reaction
(Adjustment no longer cor-
rect)
Error tolerance time in
seconds
Fiessler Elektronik GmbH & Co. KG
Buchenteich 14, D-73773 Aichwald
A correction of the current number of persons present can be entered here
Enter the maximum number of persons allowed.
By default 1 person per 20 m² and available area 300 m²:
Input = 15 (300 / 20 = 15)
By default 1 person per 10 m² and available area 300 m²:
Input = 30 (300 / 10 = 30)
If the permitted number of persons is exceeded, an acoustic alarm can be given.
- Alarm Active
- Alarm Disabled
The mounting location of the sensor pillar seen from the shop entrance or access must be selected.
Entering and exiting persons can only be detected correctly if the setting corresponds to the actual installation loc-
ation of the columns.
- Sensor right / reflector left
- Sensor left / reflector right
If a person stops between the pillars, or if the pillars are no longer aligned correctly, it is no longer possible to
detect the persons. The signal lamp flashes red with or without acoustic warning when the fault tolerance time is
reached.
- Signal lamp with acoustic warning
- Signal lamp without acoustic warning
Here you can set the time after how many seconds a warning should occur according to the configured error
reaction.
The error tolerance time should be chosen so large that a person walking slowly through the column does not
cause an error reaction.
Normally it is not intended that persons stay in the area of the pillars for a longer time. An error reaction time of 30
s is recommended.
If people frequently stand in the area of the pillars, the fault tolerance time can be increased accordingly.