ENGLISH
-
Photocells on opening (photc. open) [ OFF ]
ON:
In case of obscuring, this excludes photocell operation on opening.
During the closing phase, it immediately reverses the motion.
OFF: In case of obscuring, the photocells are active both on opening and
on closing. When a photocell is obscured on closing, it reverses the
motion only after the photocell is disengaged.
-
Photocell test (test phot) [ OFF ]
ON:
Activates photocell check (see fig. 17A)
OFF: Deactivates photocell check
-
Gate-open or 2nd radio channel warning light (SCA 2ch) [ ON ]
ON:
The output between terminals 14 and 15 is configured as Gate-open warn-
ing light, in this case the 2nd radio channel controls pedestrian opening.
OFF: The output between terminals 14 and 15 is configured as 2nd radio
channel.
-
Fixed code (fixed code) [ OFF ]
ON:
The receiver is configured for operation in fixed-code mode, see
paragraph on "Radio Transmitter Cloning".
OFF: The receiver is configured for operation in rolling-code mode, see
paragraph on "Radio Transmitter Cloning".
-
Radio transmitter programming (radio prog) [ ON ]
ON:
This enables transmitter storage via radio:
1 – First press the hidden key (P1) and then the normal key (T1, T2,
T3 or T4) of a transmitter already memorised in standard mode by
means of the radio menu.
2 – Within 10s press the hidden key (P1) and the normal key (T1, T2,
T3 or T4) of a transmitter to be memorised.
The receiver exits the programming mode after 10s, other new trans-
mitters can be entered before the end of this time.
This mode does not require access to the control panel.
OFF: This disables transmitter storage via radio.
The transmitters can only be memorised using the appropriate Radio
menu.
-
Start-Open selection (start-open) [ OFF ]
ON:
The input between the two terminals 3-4 acts as open.
OFF: The input between the two terminals 3-4 acts as start.
-
PED-CLOSE selection (ped-close) [ OFF ]
ON:
The input between the two terminals 16-17 works as CLOSE.
OFF: The input between the two terminals 16 and 17 works as PARTIAL
OPENING.
-
Master/Slave (Master) [ OFF ]
ON:
The control panel is set as Master in a centralised connection.
OFF: The control panel is set as Slave in a centralised connection.
8.4) Radio Menu (radio)
- Add
Allows you to add one key of a radio control device to the receiver memory;
after storage it displays a message showing the receiver number in the
memory location (from 01 to 64).
- Add Start button (add start)
associates the required key to Start command
- Add 2ch button (add 2ch)
associates the required key to 2nd radio channel
For transmitters with hidden key, press hidden key P1 (fig. B1A). For transmit-
ters without hidden key, the key P1 function corresponds to simultaneously
pressing the 4 transmitter keys or, after opening the battery compartment,
bridging the two P1 points by means of a screwdriver (fig. B1A).
- Read (read)
Checks one key of a receiver; if stored it displays a message showing
the receiver number in the memory location (from 01 to 64), and the key
number (T1, T2, T3 or T4).
- Delete (erase 1)
Removes one single key of a transmitter from the receiver memory; after
deletion it displays a message showing the receiver number in the memory
location (from 01 to 64).
- Eliminate list (erase 64)
WARNING! Completely removes all memorised radio control devices from
the receiver memory.
8.5) Language Menu (Language)
Allows you to set the language on the display programmer.
5 languages are available:
-
ITALIAN (TA)
-
FRENCH (FRA)
-
GERMAN (DEU)
-
ENGLISH (ENG)
-
SPANISH (ESP)
1 -
BOTTICELLI VENERE D
Downloaded from
www.Manualslib.com
INSTALLATION MANUAL
manuals search engine
8.6) MENU DEFAULT (DEFAULT)
Restores the preset default values on the control unit. After restoring, a new
autoset operation must be carried out.
8.7) DIAGNOSTICS AND MONITORING
The display on the VENERE D panel shows some useful information, both
during normal operation and in the case of malfunctions.
Diagnostics:
In the case of malfunctions, the display shows a message indicating which
device needs to be checked:
STRT
= START input activation
STOP
= STOP input activation
PHOT
= PHOT input activation
FLT
= FAULT input activation for checked photocells
SWO
= input activation OPENING LIMIT SWITCH
SWC
= input activation CLOSING LIMIT SWITCH
PED
= input activation PEDESTRIAN
OPEN
= OPEN input activation
CLS
= CLOSE input activation
In the case where an obstacle is found, the VENERE D panel stops the door
and activates a reverse manoeuvre; at the same time the display shows the
"BAR" message.
Monitoring:
During the opening and closing phases, the display shows four digits sepa-
rated by a dot, for example 35. 4 0.
Figures are constantly updated during the manoeuvre and represent the
instant torque reached by motor 1 (35) and threshold torque (opening, clos-
ing, slow-down) set in the parameter menu (40).
These values allow the torque setting to be corrected.
If the istant torque value reached during the manoeuvres turns out to be consid-
erably close to the threshold value set in the parameter menu, future operation
failures are likely to occur due to wearing or small door deformations.
It is therefore advisable to check the maximum torque reached during some
of the manoeuvres carried out in the course of installation, and if necessary
set a value about 5-10 percent points higher in the parameter menu.
8.8) AUTOSET MENU (Autoset)
•
Bring the door to its closing position.
•
Initiate an autoset operation by moving to the appropriate VENERE D
panel menu (Fig.B).
•
As soon as the OK button is pressed, the following message will be di-
splayed ".... .... ....", and the control unit initiates an opening manoeuvre
followed by a closing manoeuvre, during which the minimum torque value
needed for door movement will be automatically set.
During this phase, it is important to avoid obscuring the photocells, as
well as using the START and STOP commands and the display.
•
By the end of this operation, the control unit will have automatically set
the optimum torque values. Check and, if necessary, modify them as
described in the programming section.
WARNING: Check that the impact force value measured at
the points established by the EN 12445 standard is lower than that
specified in the EN 12453 standard.
WARNING! During the autoset phase, the obstacle detection
function is not optimised; the installer must check the operator
movement and prevent persons and things from coming near or stop-
ping within the operating range.
8.9) LIMIT-SWITCH ADJUSTMENT MENU
The VENERE D control panel is provided with an adjustment menu for opening
and closing limit switches, which simplify the installation procedure.
Making reference to Fig. 18 and 19, and Fig. B showing control panel pro-
gramming, proceed as follows:
•
Initiate a limit-switch adjustment operation by moving to the appropriate
VENERE D panel menu (Fig.B).
•
When the "CLOSE" message is displayed, bring the door to the required
closing position using the "+" and "-" control unit buttons, keeping in mind
that the "-" button closes the door whereas the "+" button opens the door.
As soon as the door is in the required closing position, press the "OK"
button in order to memorise the closing limit-switch position.
•
When the "OPEN", message is displayed, bring the door to the required
opening position using the "+" and "-" control unit buttons. As soon as the
door is in the required opening position, press the "OK" button in order
to memorise the opening limit-switch position.
•
Correctly position the "carriage lock" next to the carriage (fig.18 ref.6
A-B).