G e n e r a l i n f o r m a t i o n :
EX4-8 are stepper motor driven valves for precise
control of refrigerant mass flow in refrigeration, air
conditioning, heat pumps, industrial cooling process
and close control systems as:
- expansion valves and liquid injection valves
- suction pressure regulator (evaporator or crankcase)
- hot gas bypass regulator
- hot gas flow such as heat reclaim application
- Condensing pressure regulator and liquid duty
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure to
comply can result in device failure, system damage
or personal injury.
• According to EN 13313 it is intended for use by
persons having the appropriate knowledge and
skill.
• Before opening any system make sure pressure in
system is brought to and remains at atmospheric
pressure.
• Do
not
release
any
refrigerant
atmosphere!
• Do not exceed the specified maximum ratings for
pressure, temperature, and voltage.
• Do not operate system before all cable connections
are completed.
• Do not operate valve connected directly to supply
voltage. Use suitable stepper motor driver.
• Do not operate the valve when the compressor is
not running.
• Do not operate the valve when system is under
vacuum except for closure of valve before
refrigerant charging.
• Before installation or service disconnect all
voltages from system and device.
• Do not use any other fluid media without prior
approval of EMERSON. Use of fluid not listed
could result in a change of hazard category of
product and consequently change of conformity
assessment requirement for product in accordance
with European pressure equipment directive
2014/68/EU.
• Ensure that design, installation and operation are
according
to
European
standards/regulations.
M o u n t i n g l o c a t i o n : ( F i g . 1 , 2 )
Expansion valve and liquid injection applications:
- The motor needs to be pointed between downward to
sideways. (Fig. 1)
- For best result, locate the valve as close as possible to
the distributor or inlet of evaporator.
T e c h n i c a l D a t a :
Type
Maximum working pressure PS
Factory pressure Test PT
Hazard category:
PED 2014/34/EU
PED Conformity Assessment
Fluid group (acc.PED)
Refrigerants
Operating temperature
Dimensions
Nominal Supply Voltage U
Maximum Current Imax
Winding resistance per phase /
isolation resistance
Markings
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Electrical Control Valves EX4-8
- Check for sufficient refrigerant charge/subcooling
and make sure no flash gas is present at the inlet of
valve before attempting to check valve operation.
Install an sight glass as well as a filter drier before the
valve.
Hot gas bypass applications:
- The motor needs to be pointed downward.
- Install the valves as far as possible from compressor
discharge.
- It is also recommended to install a check valve (
on main hot gas pipe going to condenser after branch
line into the valve (
Suction line application:
- The motor needs to be pointed downward.
Oil free system:
- The motor needs to be pointed downward.
I n s t a l l a t i o n :
• Direction of refrigerant flow must match with arrow
on the label (except bi-flow valves).
Warning:
• All valves are delivered at half open. Do not charge
into
the
system before closure of valve. See operating
instruction of used driver/controller.
• The interior parts of valve must be protected
against moisture and water at any time. It is not
permitted the use of water, steam or any other
solvent to the inside of valve for cleaning purpose.
B r a z i n g : ( F i g . 3 )
• Perform and consider the brazing joint as per
EN 14324.
• Before and after brazing clean tubing and brazing
joints.
• Minimize vibrations in the piping lines by appropriate
solutions.
• Do not exceed the max. body temperature of
120°C!
• Use flux and silver rod having a minimum of 30%
silver.
P r e s s u r e T e s t :
After completion of installation, a pressure test must be
carried out as follows:
- according to EN 378 for systems which must
comply
and
national
directive 2014/68/EU.
- to maximum working pressure of system for other
applications.
Warning:
• Failure to do so could result in loss of refrigerant
and personal injury.
• The pressure test must be conducted by skilled
EX4
90 bar (uni-flow),
60 bar (bi-flow)
UL Approval: all 60 bar
99 bar (uni-flow),
66 bar (bi-flow)
-
-
A1:
R744 (subcritical), R448A, R449A, R513A, R450A, R134a, R452A, R23, R410A, R407C,
R404A, R507, R124
A2L:
R1234ze, R32, R452B, R454B, R454A, R454C, R123yf
at inlet:
Uni-flow: –50*... +100°C, Bi-flow: -50*...+80°C
at outlet:
-100*...+100°C
24 VDC
0.5 A
14 Ω ± 10% /
> 20 MΩ
www.emersonclimate.eu
Operating instructions
) (Fig. 2).
with
European
pressure
EX5
EX6
60 bar
60 bar
66 bar
66 bar
-
-
I (listed A2L refrigerants) & II (listed A1 refrigerants)
see Fig. 4
24 VDC
24 VDC
0.5 A
0.5 A
14 Ω ± 10% /
14 Ω ± 10% /
> 20 MΩ
> 20 MΩ
persons with due respect regarding the danger
related to pressure.
L e a k a g e T e s t :
Conduct a tightness test according to EN 378 with
appropriate equipment and method to identify leakages
of external joints. The allowable leakage rate must be
according system manufacturer's specification.
E l e c t r i c a l C o n n e c t i o n :
)
Warning:
• Entire electrical connections have to comply with
local regulations.
• Improper wiring will result wrong direction of
rotation or no rotation of stepper motor
• Prewired plug (EXV-M...) are not in compliance with
EN60335-1-40/89 and are ready for connection to the
valve.
• There is no specific requirement for positioning of
plug on pins (see Fig.5): Push the plug on pins on top
of the valve. Rotate the nut one turn in clockwise
direction and push the plug. Repeat this procedure
until the plug is tightened.
Wiring / Mounting to driver/Controller:
See the wiring diagram of applied driver/controller.
O p e r a t i o n :
• See operating instructions of applied electronic
driver/controller.
S e r v i c e / M a i n t e n a n c e :
• Defective EX valves must be replaced, they cannot
be repaired.
• For motor check:
- Remove cable plug from valve.
- Use an ohmmeter with suitable range.
- Measure windings resistance per phase at opposite
placed pins acc. Fig.6 and data as in the table below.
• EX4-8 has capability of positive shut-off when it is
driven to fully close position (as long as inlet pressure
is 0.5 bar above outlet pressure).
equipment
EX7
60 bar
86 bar
-
II
-
Module D1
24 VDC
0.75 A
10 Ω ± 10% /
> 20 MΩ
,
1017
EX4-8_OI_EN_DE_FR_ES_IT_RU_R08_865288.docx
EX8
45 bar
65 bar
II
Module D1
Note:
UL Approval: only A1
refrigerants
*) UL Approval: ≥ - 40°C
24 VDC
0.8 A
7.5 Ω ± 10% /
> 20 MΩ
,
1017
Date: 28.04.2020

Werbung

loading

Inhaltszusammenfassung für Emerson EX serie

  • Seite 1 • Do not use any other fluid media without prior 120°C! driven to fully close position (as long as inlet pressure approval of EMERSON. Use of fluid not listed • Use flux and silver rod having a minimum of 30% is 0.5 bar above outlet pressure).
  • Seite 2 - Steckerkabel vom Ventil entfernen. und das Bauteil spannungsfrei zu schalten. auszuführen. - Ohmmeter mit geeignetem Bereich verwenden. • Es dürfen nur von EMERSON freigegebene • Vor und nach dem Löten sind die Lötstellen zu - Wicklungswiderstände Phase Medien eingesetzt werden. Die Verwendung nicht reinigen.
  • Seite 3 • No use ningún fluido que no haya sido previamente puede ser reparado. soldadura. aprobado por EMERSON. El uso de sustancias no • Para comprobación del motor: • Minimice las vibraciones en las tuberías mediante la aprobadas puede dar lugar a un cambio en la - Retirar el cable conector de la válvula.
  • Seite 4 • Ne pas utiliser un autre fluide que ceux indiqués • Minimiser les vibrations des tuyauteries par des - Utiliser un ohmmètre avec une plage de mesure sans l’approbation obligatoire d’EMERSON. équipements appropriés. appropriée. L'utilisation d'un fluide non approuvé peut •...
  • Seite 5 • Non utilizzare altri fluidi senza la previa • Verifica del motore: • Pulire i tubi e le giunture prima e dopo la brasatura. approvazione di EMERSON. L’uso di refrigeranti - Rimuovere il connettore dalla valvola. • Ridurre il più possibile le vibrazioni sulle tubazioni...
  • Seite 6 7.5 Ω ± 10% / сопротивление изоляции > 20 MΩ > 20 MΩ > 20 MΩ > 20 MΩ > 20 MΩ маркировка 1017 1017 Emerson Climate Technologies GmbH www.emersonclimate.eu Date: 28.04.2020 Am Borsigturm 31 I 13507 Berlin I Germany EX4-8_OI_EN_DE_FR_ES_IT_RU_R08_865288.docx...
  • Seite 7 7/8" x 7/8" (22 x 22 mm) EX6-I31 1-1/8" x 1-1/8" EX6-M31 28 x 28 mm EX7-U31 1-1/8" (35 mm) x 1-1/8” (35 mm) Emerson Climate Technologies GmbH www.emersonclimate.eu Date: 28.04.2020 Am Borsigturm 31 I 13507 Berlin I Germany EX4-8_OI_EN_DE_FR_ES_IT_RU_R08_865288.docx...

Diese Anleitung auch für:

Ex4Ex5Ex6Ex7Ex8