WARNING
Unsuitable cables and/or cable glands
Danger of explosion in hazardous areas.
Only use suitable cables and cable glands complying with the requirements specified in Chapter "Technical data
•
(Page 9)".
Tighten the cable glands in accordance with the torques specified in Chapter "Technical data (Page 9)".
•
When replacing cable glands use only cable glands of the same type.
•
After installation check that the cables are seated firmly.
•
Requirements
You need the EMC filter module with article number C73451-A430-D23 for the electrical connection of an external position
detection system, article number C73451-A430-D78, to the positioner.
Wiring diagram
①
EMC filter module terminals
②
Positioner with integral EMC filter module C73451-
A430-D23
③
Yellow wheel for locking the position detection
④
Ribbon cable connector of fitted potentiometer, or
ribbon cable connector of EMC filter module
⑤
Basic electronics
⑥
Screw
⑦
EMC filter module C73451-A430-D23
Figure 5-1
Connection to positioner
Preparing the positioner
1. You have performed the steps described in the section "Auto-Hotspot".
8
⑧
External position detection system C73451-A430-
D78
⑨
External position detection system terminals
⑩
External position detection system cable gland
⑪
Cable
⑫
EMC filter module cable gland
⑬
Input signal for positioner
SIPART PS2 external position detection system
A5E03830794-03, 09/2014