8.7 Supply voltage
AC power supply:
DC power supply:
8.8 Sensor supply voltage
AC power supply:
DC power supply:
8.9 Climatic Conditions
Operating temperature:
Storage temperature:
Relative air humidity:
Altitude:
8.10 EMC
Noise immunity:
Noise emission:
17
90...260 V AC/max. 12 VA
50/ 60 Hz
ext. fuse protection: T0,1 A
24 V AC +/-10%/max.
7 VA 50/60 Hz
ext. fuse protection:
T 0,315 A
10...30 V DC/ max. 5,5W
at max. nominal load re-
verse polarity protection
ext. fuse protection
T 0,315 A
24 V DC -20/+15%, 50mA
max. 50 mA, external
voltage supply is con-
nected through
-20°C .. +65°C
-25°C .. +75°C
93% at +40°C,
non-condensing
up to 2000 m
EN61000-6-2
with shielded signal and
control cables
EN55011 Class B
8.11 Device safety
Design to:
Protection Class:
Application area:
8.12 Mechanical data
Housing:
Dimensions:
Panel cut-out
Installation depth:
Weight:
Protection:
Housing material:
Vibration resistance: 10 - 55 Hz/1 mm/XYZ
(EN60068-2-6):
Shock resistance:
(EN60068-2-27):
Shock resistance:
(EN60068-2-29)
Cleaning:
8.13 Connections
Supply voltage and outputs:
Plug-in screw terminal, 7-pin, pitch 5.08
Core cross section: max. 2.5 mm²
AWG 22-12
solid wire, rigid 0.34-2.5 mm²
fine wire without cable terminal
0.34-2.5 mm²
fine wire with cable terminal
0.34-2.5 mm²
Signal and control inputs:
Plug-in screw terminal, 8-pin, pitch 3.81
Core cross section: max. 1.5 mm²
AWG 28-16
solid wire, rigid 0.14-1.5 mm²
fine wire without cable terminal
0.14-1.0 mm²
fine wire with cable terminal
0.25-1.0 mm²
EN61010 Part 1
measurement category 2
pollution degree 2
Panel-mount housing
to DIN 43 700, RAL7021
48 x 48 x 91 mm
+0,6
+0,6
45
x 45
mm
approx. 107 mm including
the terminals
approx. 125 g
IP 65 (front)
Polycarbonate UL94 V-2
30 min in each direction
100g/2ms/XYZ
3 times in each direction
10g/6ms/XYZ
2000 times in each
direction
The front of the unit
should only be cleaned
using a soft damp
(water!) cloth.