Duct Smoke Detector
6
Configuration
6.1
Jumper setting
Figure 6.1: Jumper setting
No.
FAD-420-HS-EN Connection Board
2-3
1-2
FAD-RB-DIBT Relay Board
1-2
2-3
Notice!
Adjust the sensitivity of the detector by using the programming software on the control panel.
Please refer to the software's online help.
6.2
Checking the airflow
Optional: To ensure that the system is functioning correctly, check that the air speed enables
a sufficient differential pressure to be set in the device. This can be done by using a
manometer. The air speed in the duct should read between 1.5 m/s and 20 m/s. The
differential pressure between the sample tubes must measure within the following range:
Bosch Sicherheitssysteme GmbH
Configuration
Tamper switch deactivated (default)
Tamper switch activated
Relay drops out if there is no power and/or the detector C point is activated.
Relay switches on if the detector C point is activated
Installation Guide
Product description | en
223
2015.03 | 6.0 | F.01U.033.733