Temperature Input Module for Zone 1 / Div. 1
Series 9482/32
• Position the module vertically at
the intended slot of the BusRail and
press lightly to snap it into place.
• Press the module down onto the
BusRail to ensure that it is properly
secured! There should not be any
gap between the module and BusRail!
The module must not be able to
disconnect without the handle being
actuated.
• Plug the pluggable terminals X1 and
X2 into the module and secure them
against loosening using safety screws
(tightening torque 0.5 to 0.6 Nm).
• To ensure a distance of at least
50 mm between the intrinsically safe
20761E00
and non-intrinsically safe electrical
circuits, if necessary, mount a partition
(220101) on the adjacent Ex i module
or leave a space between the Ex i and
non-Ex i modules.
Note:
The partition can only be mounted
on Ex i modules. If the Ex i module
has 2 terminal blocks, the partition
must be machined further
(predetermined breaking point).
2073E00
218149 / 948260310010
2019-07-29·BA00·III·en·03