3 Installation
3.1 Installation Instructions
3.2 Fitting the device
→
Please follow the mechanical and electrical installation instruc-
tions in the enclosed instruction leaflet IL03402019Z (previously
AWA1210-2490).
▶
Mount the motor-protective circuit-breaker only as shown in figure 9.
≧ 1 5 m m
(≧ 0 .6 " )
≧ 1 5
≧ 1 5
Figure 9: Approved mounting position for PKE motor-protective circuit-breakers
▶
Wire the motor cables.
I > I > I >
Figure 10:Main current wiring
The following maximum cable cross sections are possible.
Table 5: Maximum conductor cross-sections of the PKE12/PKE32 motor cables
2 x (1 - 6 mm
2 x (1 - 4 mm
UL
AWG14 - 10
Cu 75 °C
PKE12, PKE32, PKE65 11/17 MN03402004Z-DE/EN www.eaton.com
Typ
PKE12(-AK), XTPE012B(NL)
PKE32(-AK), XTPE032B(NL)
PKE65(-AK), XTPE065D(NL)
I > I > I >
2
)
1.7 Nm (15 lb-in)
2
)
1.7 Nm (15 lb-in)
1.8 Nm (16 lb-in)
Wire
3.1 Installation Instructions
a
→ I
q
55 mm
50 kA
(2.17'')
90°
110 mm
100 kA
(4.33'')
55 mm
(2.17'')
3 Installation
90°
90°
41