Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze E82ZAFBC001 Montageanleitung Seite 40

Bus-i/o für motec 0,55...2,2 kw
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5
Electrical installation
Wiring
X3/
Signal type
62
Analog
output
7
8
Analog
input
9
20
28
3)
E1
3)
E2
Digital
inputs
E3
E4
39
A1
Digital
output
59
1)
Output level 0 … +10 V: Adapt offset (C0109/C0422) and gain (C0108/C0420)
2)
Adjust offset (C0026) and gain (C0027) separately for each function module:
After replacing the function module or the standard device
After loading the Lenze setting
3)
Alternatively frequency input 0 … 10 kHz single−tracked or 0 ... 1 kHz double−tracked, configuration
via C0425
40
Function
Output frequency
GND1,
reference potential for analog signals
Input for actual value or setpoint
Change range using the DIP switch and C0034
l
Voltage signal
l
Current signal
Internal, stabilised DC voltage supply for setpoint
potentiometer
Internal DC voltage supply for control of digital
inputs and outputs
Controller inhibit (CINH)
Activation of JOG frequencies
JOG1 = 20 Hz
JOG2 = 30 Hz
JOG3 = 40 Hz
DC−injection brake (DCB)
Change of direction of rotation
CW/CCW rotation
GND2,
reference potential for digital signals
Ready for operation with
– internal supply:
– external supply:
DC supply for X3/A1
– internal (jumper to X3/20):
– external:
l
Level
(Lenze setting: Bold print)
0 … +6 V
0 … +10 V
1)
0 … +5 V
0 … +10 V
−10 V … +10 V
2)
0 … +20 mA
+4 … +20 mA
+4 … +20 mA (open−circuit
monitored)
+5.2 V
+20 V ±10 % (ref.: X3/7)
1 = enable
E1
JOG1
1
JOG2
0
JOG3
1
1 = DCB
E4
CW
0
CCW
1
0 … +20 V
0 … +24 V
+20 V
+24 V
EDK82ZAFBC−001 DE/EN/FR 7.2
E2
0
1
1

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis