Motor-protective circuit-
breaker PKE12, PKE32 and
PKE65
40
The rated operational current and the tripping class must be
set on all trip blocks PKE-XTU(W)(A)-...
In addition, PKE-XTU(W)A-... trip blocks can be used to
transmit operational data (such as instantaneous current
values and trip reasons) to a higher-level field bus system via
SmartWire-DT. These communication tasks do not affect the
device's motor protection function in any way.
For more information, please consult the manual
h
MN05006001Z-EN (previously AWB2723-1613).
It is availalbe for download on the Internet.
http://www.eaton.com/moellerproducts
h
Notice!
PKE12, PKE32, and PKE65 units are approved for use as
protection devices for explosion-proof electric motors
when used together with PKE-XTU(W)-... trip blocks.
Using PKE motor-protective circuit-breakers with PKE-
XTU(W)A-... advanced trip blocks to protect explosion-
proof electric motors and to transmit operational data is
only allowed in combination with the functional element
PKE-SWD-SP.
Table 9:
Part no.
PKE12/XTU(A)-1.2
PKE12/XTU(A)-4
PKE32/XTU(A)-4
PKE12/XTU(A)-12
PKE32/XTU(A)-12
PKE32/XTU(A)-32
PKE65/XTUW(A)-32
PKE65/XTU(A)-65
Setting range of the PKE motor-protective circuit-
breaker
Setting range I
[A]
0.3 - 1.2
1 - 4
3 - 12
8 - 32
8 - 32
16 - 65
10/15 MN03402004Z-DE/EN