Type 8025 UNIVERSAL
Installation and wiring
7.4.3
Wiring a panel version
Only▶move▶the▶selectors▶when▶the▶power▶supply▶is▶off.
→
▶
Install▶the▶device▶as▶described▶in▶chap.▶„7.2".
→
▶
Set▶the▶selectors▶"SENSOR▶TYPE",▶"SENSOR▶SUPPLY"▶and▶
"LOAD":▶see▶chap.▶„7.4.10".
→
▶
Before▶wiring▶the▶device▶insert▶the▶sup-
plied▶cable▶clips▶into▶the▶slots▶of▶the▶elec-
tronic▶board.
Fig. 11: Inserting the cable clips
→
▶
Wire▶acc.▶to▶chap.▶„7.4.5"▶,▶„7.4.6",▶„7.4.9"▶and▶„7.4.10".▶
→
▶
Secure▶the▶power▶supply▶cable,▶the▶flow▶sensor▶connection▶
cable▶and,▶depending▶on▶the▶version,▶the▶relay▶connection▶
cables,▶with▶the▶cable▶clips.
7.4.4
Wiring a wall-mounted version
Only▶move▶the▶selectors▶when▶the▶power▶supply▶is▶off.
Insert▶the▶supplied▶stopper▶gaskets▶into▶the▶unused▶cable▶
glands▶to▶ensure▶the▶tightness▶of▶the▶device.
•▶ Unscrew▶the▶unused▶cable▶gland.
•▶ Remove▶the▶transparent▶disk.
•▶ Insert▶the▶supplied▶stopper▶gasket.
•▶ Screw▶the▶nut▶of▶the▶cable▶gland.
→
▶
Install▶the▶device▶as▶described▶in▶chap.▶„7.3".
→
▶
Set▶the▶selectors▶"SENSOR▶TYPE",▶"SENSOR▶SUPPLY"▶and▶
"LOAD":▶see▶chap.▶„7.4.10".
→
▶
If▶the▶wall-mounted▶version▶is▶energized▶with▶a▶115/230▶V▶AC▶
power▶supply,▶set▶selector▶
Selector▶ E ▶makes▶it▶possible▶to▶configure▶the▶supply▶volt-
age▶of▶the▶device▶in▶a▶115/230▶V▶AC▶version.
→
▶
Energize▶the▶
device▶with▶
a▶230▶V▶AC▶
voltage.
Fig. 12: Selector of the supply voltage on a 115/230 V AC version
→
▶
Loosen▶the▶nuts▶of▶the▶cable▶glands.
English
E
▶as▶shown▶in▶„Fig.▶12".
E
→
▶
Energize▶the▶
device▶with▶
a▶115▶V▶AC▶
voltage.
19