Measurement assembly on an open container
h
Lower filling level
U
h
Upper filling level
O
p
Pressure
Assembly on a closed container
When taking measurements in a closed container without or with little condensate formation, the negative pressure line is
not filled. Lay the line in such a way that pockets of condensate do not form. Install a condensation container if required.
Measurement assembly on a closed container (no or little condensate
separation)
h
Lower filling level
U
h
Upper filling level
O
p
Pressure
SITRANS P DS III/P410 (7MF4.33.. 7MF4.34.. 7MF4.35..)
A5E03434626-04, 05/2015
Formula:
Start of scale value: p
Full-scale value: p
Δp
Start of scale value
MA
Δp
Full-scale value
ME
ρ
Density of the measured medium in the container
g
Acceleration due to gravity
Formula:
Start-of-scale value: Δp
Full-scale value: Δp
Δp
Start of scale value
MA
Δp
Full-scale value
ME
ρ
Density of the measured medium in the container
g
Acceleration due to gravity
= ρ · g · h
MA
U
= ρ · g · h
ME
O
= ρ · g · h
MA
U
= ρ · g · h
ME
O
19