Technical Data
Indication
LED indication
"Plant STOP"
24 V external supply
Module requires
maintenance
Operating state
Group error
Channel error
Channel status
Function indication
Retrievable
parameters
Error indication
Module status and
alarms
Signal errors for
each channel
Signal status bit
Open circuit
Short circuit
Mounting / Installation
Installation position
Mounting type
For further technical data, see r-stahl.com.
230244 / 947260310010
2019-03-08·BA00·III·en·01
"24 V" LED, yellow
"24 V" LED, green
"M/S" LED, blue
"RUN" LED, green
"ERR" LED, red
LED, red for each channel
LED, yellow for each channel
Manufacturer, type, hardware revision, software revision, serial number
• Primary / redundant internal bus error
• No response from IOM
• Configuration does not correspond to the module
• Hardware error
• Excess temperature
• Slot error
• Module requires maintenance
"1" = signal interfered; "0" = signal valid
NAMUR signal:
I < 100 μA
3-conductor PNP
U
< 1.6 V
IN
proximity switch:
Output:
I < 30 μA in ON state
R > 800 Ω in OFF state
NAMUR signal:
R < 100 Ω
3-conductor PNP
U
< 1.6 V
IN
proximity switch:
Output:
I > 500 mA in ON state
R < 25 Ω in OFF state
Horizontal or vertical (observe operating instructions)
on 35 mm DIN rail NS 35/15 (DIN EN 60715)
Digital Input Output Module 24 V
for Ex n Zone 2
Series 9472/35
Technical Data
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
15