FLM-420-I8R1-S

Technical specifications

LSN input voltage
Max. current consumption from LSN
Inputs
1. Line monitoring with EOL:
-
EOL resistor
-
Overall line resistance R
(R
= R
+ R
+ R
Σ
L/2
L/2
2. Contact monitoring:
-
Max. current strength (current pulse)
Minimum activation time of the inputs IN 1 - 8
Maximum cable length of all inputs and outputs
which are connected to the loop or stub and not
electrically isolated from LSN
Change-over relay (low voltage)
Contact load (resistive load)
-
Max. switched current and voltage
-
Min. switched current and voltage
-
Max. AC frequency
Permissible wire diameter
Permissible operating temperature
Permissible storage temperature
Permissible rel. humidity
Protection class as per IEC 60529
Classes of equipment as per IEC 60950
Housing material and color
Dimensions (W x H x D)
Bosch Sicherheitssysteme GmbH
Σ
)
EOL
15 to 33 V DC
5,5 mA
8, independent
Nominal 3,9 kΩ
In standby: 1500 Ω - 6000 Ω
-
Short-circuit: < 800 Ω
-
Interruption: > 12000 Ω
-
8 mA
3,2 s
500 m in total
NC contact/COM, COM/NO contact
2 A / 30 V DC; 0.5 A / 42.4 V AC
0.01 mA / 10 mV DC; 0.01 mA / 10 mV AC
100 Hz
2
0.6 to 3.3 mm
-20 °C to +65 °C
-25 °C to +80 °C
<96 %, non-condensing
IP 54
Class III equipment
ABS+PC-FR, signal white (RAL 9003)
Approx. 140 mm x 200 mm x 48 mm