Condensate drain
When the condensate collection tank is full, the drain pump switches on automatically for 70 s and the corresponding
sensor checks the level. A locking alarm is displayed if the condensate level does not fall within the pre-set time. After
having checked the discharge pipe and resolved the drain lock, you can reset the error and the device will resume
operation (answer "YES" on "UNLOCK").
MAIN MENU
USE MENU
ALARM
SETUP
F
T ext Probe
A fault on the external temperature sensor generates this non-locking error (only the heat pump locks). After having
resolved the problem (through Technical Service intervention), you can reset the error (answer "YES" for "CALL
SERVICE").
MAIN MENU
USE MENU
ALARM
SETUP
F
NOTE: the system does not automatically call Technical Service.
SETUP
You can access the Date and Hour setting and weekly programming with this option
USE MENU
MAIN MENU
ALARM
SETUP
INFO
F
ALARM
CHECK
TUBE
UNLOCK?
F
ALARM
EXT PROBE
CALL
SERVICE
F
SETUP
DATE&HOUR
PROGRAM
F
YES
YES