TYPE 00 - 01 - 03 ONLY: Adjustment of the closing stroke margin: it adjusts the duration of the last part of
the stroke during which an obstacle is interpreted as a stroke, blocking the motor without performing the
inversion.
For motors with encoders, the set value indicates the number of revolutions of the rotor; while for motors
without encoder, the value is expressed in% of the maximum stroke.
Warning: for motors without encoder, if P036 (duration slow-down while closing) is >10%, it forces the stroke
detection margin so that it's the same than the slow-down.
TYPE 02 ONLY: Adjustment of the stop-margin in closing: adjusts the duration of the last part of the closing
movement, in which an obstacle is seen as a stop, causing the motor to stop without reversal on the obstacle.
The value is expressed in number of revolutions of the rotor.
TYPE 00 - 01 - 03 ONLY: Operators force adjustment at stroke arrival - If=0, setting off (the force value on
the stroke is calculated automatically) - If≠0 (operators with encoder) it indicates the force value (expressed
in% of the max value) set in the last length - If≠0 (operators without encoder), max speed is activated during
last length.
TYPE 02 ONLY: Force adjustment in the stop margin in closing, its duration is set through P059.
"Energy saving" mode: If=1 after 10sec of inactivity, the control panel turns the 24V outputs and the display
off that will be turned on at first command received (use recommended battery-powered and / or solar
panel).
Warning: when "Energy saving" is enabled, SAS function is not available.
Warning: when "Energy saving" is enabled, only the stabilized output 24V_ST must be used to power
accessories.
Electric-lock output operating: If=0 "boost" output for electric-lock art.110 power supply, If=1 24V output
controlled by the ELOCK_IN input as pulsed mode,If=2 24V output controlled by the ELOCK_IN input as
step-by-step mode, If=3 electro-brake output for not self-locking operators, If=4 24V output for electric-lock
power supply via an external relay, If=5 24V output for electro-magnets power supply for barriers, If>5 24V
output controlled by the ELOCK_IN input as temporized mode (the set value indicates the switch-off delay in
seconds).
Run direction inversion: If=1 automatically reverses the outputs open/close of the operators, avoiding having
to manual change the wiring when installing the operator in an inverted position.
Warning: Changing this parameter you need to change the parameters for the opening and closing limit
switches.
Unused parameter
Maintenance Operations-counter: if = 0 reset the counter and disables the intervention request , if>
0 indicates the number of operations (x 500) to be made before the control panel executes a 4 second
additional pre-flash to indicate the need of maintenance.
i.g.: If P065 = 050, operations number = 50x500 = 25000 operations
Warning: Before you set a new value of the counter-manoeuvres maintenance, the same must be reset by
setting P065= 0 and only later P065 = "new value".
Selection of operating flashing light output: If=0 intermittent flashing light output;
If=1 Fixed flashing light output (for flashing lights with intermittent interior circuits).
SAFETY 1
SAFETY 2
56
Operation of the SFT input: if = 0 safety edge always enabled, if = 1 safety edge enabled only
while closing, if = 2 safety edge enabled only while closing and before any movement, if = 3
safety edge enabled only when opening, if = 4 safety edge enabled only while opening and
before any movement; as for the obstacle detection with internal anti-crushing sensor, also the
activation of the inputs SFT1 and SFT2 causes the complete or partial reversal as set by P055
(duration of inversion on obstacles while opening, and P056 (duration of reversal on obstacle
while closing)