PRE-INSTALLATION CHECKS

The leaf must be fixed firmily on the hinges to the pillars, must not be
flexible during the movement and must move without frictions.
Before the installation of EKKO 350A, verify all dimensions etc.
There's no need for any modification, if the gate is like that shown
in Fig. 1.
Gate features must be uniformed with the standards and laws in
force. The gate can be automated only if it is in a good condition and
its conditions comply with the EN 12604 norm.
- The gate leaf does not have to have a pedestrian opening. In the
opposite case it is necessary to take the appropriate steps, in
accordance with EN 12453 norm (for instance; by preventing the
operation of the motor when the pedestrian opening is opened, by
installing a safety microswitch connected with the control panel).
- No mechanical stop shall be on top of the gate, since mechanical
stops are not safe enough.
FIXING THE ACTUATOR ATTACHMENT TO THE COLUMN
To obtain a correct movement of the leaf gate it is necessary to respect
the measures (to see the TABLES of the measures).
COLUMN ATTACHMENT FOR EKKO 350A OPERATOR
If the column is in iron, the attack can be screwed directly using four
metric screws M8.
If the column is in concrete, the attack can be fixed with four expansion
screws Ø 8 mm (Fig. 2-3).
In the case you have a wall parallel with the open gate, you must
provide a niche in which to place the operator.
FIXING THE OPERATOR ATTACHMENT TO THE GATE
(to see the TABLES of the measures).
Before inserting the pin into the gate attachment, grease
thoroughly.
Weld the base at the right height (Fig. 8).
Fix the EKKO 350A and try several times to open and to close the gate,
controlling that the operator does not touch the moving gate.
EN
Parts to install meeting the EN 12453 standard
COMMAND TYPE
Skilled persons
(out of public area*)
with manned operation
A
with visible impulses
C or E
(e.g. sensor)
with not visible impulses
C or E
(e.g. remote controldevice)
automatic
C and D, or E
* a typical example are those shutters which do not have access to any public way
A: Command button with manned operation (that is, operating as long as activated)
B: Key selector with manned operation, like code EDS1
C: Adjustable power of the motor
D: Safety edges, like code ZX01/EN and/or other safety devices to keep thrust force
within the limits of EN12453 regulation - Appendix A.
E: Photocells, like code EFA1 (To apply every 60÷70cm for all the height of the
column of the gate up to a maximum of 2,5m - EN 12445 point 7.3.2.1)
USE OF THE SHUTTER
Skilled persons
Unrestricted use
(public area)
B
non possibile
C or E
C and D, or E
C and D, or E
C and D, or E
C and D, or E
C and D, or E
3