The following diagram shows switching examples of the relay output depending on the
different possible parameter settings and the flow velocity:
Hysteresis mode
Switching time-out = 0 s
Switching time-out = 2 s
Window mode
Switching time-out = 0 s
Switching time-out = 2 s
3.6.1 Switching mode of the relay output
The switching mode of the relay output can be chosen among 2 modes, either window or
hysteresis.
- Window mode: the change of state of the relay output (OUT) occurs at any threshold
detection:
Window mode (NO-wired realy)
Relay output
ON
OFF
Low threshold
CONFIGURATION
m/s
High threshold
Low threshold
RELAY OUTPUT
ON
NO-wired relay
OFF
ON
NC-wired relay
OFF
ON
NO-wired relay
OFF
ON
NC-wired relay
OFF
ON
NO-wired relay
OFF
ON
NC-wired relay
OFF
ON
NO-wired relay
OFF
ON
NC-wired relay
OFF
m/s
High threshold
16
2 s
2 s
Window mode (NC-wired relay)
Relay output
ON
OFF
Low threshold
2 s
t
m/s
High threshold
8041