E
Setup via operator panel
Switch on enable signals on X11.3 and X13.3.
Switch off start signals on X11.4 and X11.5.
Switch on mains supply.
Start Setup procedure.
Caution!
If the motor data is not entered correctly, the drive may be damaged.
Start drive via control signals or via key of operator panel.
Agile
Quick Start Guide
Setup can be selected via menu item "Setup". At first switch-on Setup is
displayed automatically.
FuLL
Complete Setup. Select for the first commissioning.
Motor
Select for only motor data measuring.
Select for commissioning of communication.
BUSCON
Dset 0
Data set query is only displayed if Setup is manually selected
via the menu item "Setup".
Choose data set 0. Another setting is only necessary for setup of various
motors.
cTRL
Control method
UF
Asynchronous motor
Foc
Asynchronous motor
SyNch
Synchronous motor
Motor typeplate (example)
V
Hz kW
A
230/400
50 0.25
1.32-0.76
voLt
P ovt
Freq
Ampere
Press for 1 s to increment or decrement each digit separately.
Entry of cosPhi in control method UF and Foc. Entry of PoLPrS (number
of pole pairs) in control method Synch.
Additional adjustments during commissioning setup):
−
Temperature evaluation at X12.4 via thermal contact, PTC, KTY,
PT100
−
Stopping behavior. Coast to stop, stop and switch off, emergency
stop and more
−
Function for energy saving
−
PID controller for process control
−
Electronic gear. Synchronization of drives.
See operating instructions.
Possible displays during commissionig (setup)
StO
Message if Enable is missing. Switch on the signal at X11.3 and X13.3.
In case of error messages refer to section ". Error messages and
SA0O--
warnings during Setup".
SF0O--
Select, if further motor parameters are to be measured automati-
tvne
cally.
Tvning
Measurement of motor data.
Select, if the data of a BONFIGLIOLI motor entered.
CALC
The pre-settings of other motor data are loaded.
Acceleration clockwise, factory setting 5Hz/ s
Acc
Deceleration clockwise, factory setting 5Hz/ s
DEC
Minimum frequency, factory setting 3,5Hz
FreqLo
Maximum frequency for speed limitation, factory setting 50Hz
FreqHi
Commissioning (Setup) completed and ready for use.
done
36
V/f-control with variable speed (default)
Field oriented control. High drive
Dynamics and accurate speed control
and torque control.
cos ϕ
min
-1
1375
0.77
SPEED
cosPhi