English
General warning
Using this Quick Setup, you can carry out quick and
EMC-correct installation of the frequency converter
in five steps. The Operating Instructions, which are
also enclosed, give other examples of installation
and describe all functions in detail.
Read the safety instructions
on this page before installing the unit.
Mechanical Installation
VLT 2800 frequency converters allow side-by-side in-
stallation. Because of the need for cooling, there
must be 10 cm free air passage above and below
the frequency converter. Drill holes in accordance
with the measurements given in section Mechanical
dimensions. Retighten all four screws.
Fit the decoupling plate to the power cables and the
earth screw (terminal 95).
Electrical Installation, power
Please note that the power terminals can be re-
moved. Connect mains to the mains terminals of the
frequency converter, i.e. 91, 92, 93 and the earth
connection to terminal 95. Fit a screened/armoured
cable from the motor to the motor terminals of the
frequency converter, i.e. U, V, W. The screen ends in
a screen connector.
MG.28.A1.62 - VLT is a registered Danfoss trade mark
®
VLT
2800 Quick Setup
Electrical Installation, control cables
Remove the front cover underneath the control
panel. Place a jumper between terminals 12 and 27.
Programming
Carry out programming on the control panel. Press
the [QUICK MENU] key to enter the Quick menu. In
this menu, parameters can be selected by means of
the [+] and [-] keys. The parameter values can be
changed by pressing [CHANGE DATA]. Changes are
programmed using the [+] and [-] keys. Finish the
change of a parameter setting by pressing
[CHANGE DATA]. A change of parameter values is
saved automatically after a mains failure. If the dis-
play shows three dots at the right, the parameter
value has more than three digits. In order to see the
value, activate [CHANGE DATA]. Press [QUICK
MENU]: Set the motor parameters that are on the
nameplate of the motor:
Motor power [kW]
Motor voltage [V]
Motor frequency [Hz]
Motor current [A]
Rated motor speed
Activate AMT:
Automatic motor tuning
Set reference range
Min. reference, Ref
MIN
Max. reference, Ref
MAX
Ramp-up time [s]
Ramp-down time [s]
parameter 102
parameter 103
parameter 104
parameter 105
parameter 106
parameter 107
parameter 204
parameter 205
parameter 207
parameter 208
5