Herunterladen Inhalt Inhalt Diese Seite drucken

Toshiba RAV-SM454SDT-E Installations-Handbuch Seite 19

Vorschau ausblenden Andere Handbücher für RAV-SM454SDT-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 78
Slim Duct Type
Thermal insulation process
Apply thermal insulation for the pipes separately
at liquid side and gas side.
For the thermal insulation to the pipes at gas side,
be sure to use the material with heat-resisting
temperature 120°C or higher.
Using the attached thermal insulation material,
apply the thermal insulation to the pipe connecting
section of the indoor unit securely without gap.
REQUIREMENT
• Apply the thermal insulation to the pipe
connecting section of the indoor unit securely
up to the root without exposure of the pipe.
(The pipe exposed to the outside causes water
leak.)
• Wrap heat insulator with its slits facing up
(ceiling side).
Indoor unit
Heat insulation pipe
(Accessory)
Union
Heat
insulator of
Flare nut
the pipe
– 18 –
Installation Manual
EN
18-EN