Herunterladen Inhalt Inhalt Diese Seite drucken

Weidmuller WAVECONTROL Serie Beipackinformation Seite 19

Stromüberwachungsmodul
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 4
DANGER
Conditions for safe use:
E. The device must be mounted in an enclosure certified
for use in Class I, Zone 2, Group IIC locations and rated
IP54 in accordance with IEC 60529 when used in Class I,
Zone 2 environment.
The device shall only be used in an area of not more than
pollution degree 2, as defined in IEC 60664-1.
The device must be installed into an end-use enclosure
where a tool is required to gain access to the internal parts.
F. Class I, Zone 2 marking information:
Class I, Zone 2, AEx nA IIC T4 Gc
Class I, Zone 2, Ex nA IIC T4 Gc X
Ambient temperature range: 0 °C to +55 °C
G. Reference to standards used for evaluation of this device:
UL 508-17th Edition
ANSI/ISA 12.12.01, 2012
UL 60079-0 Edition 5, UL 60079-15 Edition 3
CAN/CSA C22.2 No. 142-M1987, 213-M1987
CSA C22.2 NO. 60079-0:11 Edition 2
CSA C22.2 NO. 60079-15:12 Edition 3
H. WAS Models only!
Information on suitable wire size and torque:
30-12 AWG for single wire, 30-14 AWG for two wires,
required torque of 4.5 to 5 lb-in. (0.51 to 0.56 Nm)
Wiring has to be suitable for a temperature of min. 90 °C.
19

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis