7 Einstellungen
Object Name
Bn 1645 Legionella funct setpoint
Bn 1646 Legionella funct duration
Bn 1646 Status
Bn 1646 Command
Bn 1663 DHW circulating setpoint
Bn 8003 State DHW
Object Name
DHW storage tank
Bn 8830 DHW temp 1
Bn 8830 Status
Bn 8832 DHW temp 2
Bn 8832 Status
Bn 5030 DHW charging time limitation
Bn 5030 Status
Bn 5030 Command
Bn 5020 DHW flow setpoint boost
Bn 5024 DHW switching differential
Bn 5050 DHW charging temperatrure max
Bn 8820 State DHW pump
Bn 8820 Status
Bn 8825 DHW pump speed
Bn 8825 Status
Bn 8826 DHW intermediate circuit pump speed
Bn 8826 Status
Bn 8831 DHW temperature setpoint current
Bn 8831 Status
Bn 8835 DHW circulating temperatur
Bn 8835 Status
Bn 8836 DHW charging temperature
Bn 8836 Status
Bn x0 State DHW circulating pump (Q4)
Bn x1 Status
Bn x2 DHW intermediate circuit pump (Q33)
Bn x3 Status
Object Name
Consumer circuit 1
Bn 1859 Flow temp setp cons request
Bn x5 State CC1 pump (Q15)
Bn x6 Status
Object Name
Consumer circuit 2
Bn 1909 Flow temp setp cons request
Bn x7 State CC2 pump (Q18)
Bn x8 Status
Object Name
Swimming pool
Bn 1959 Flow temp setpoint
Bn 8011 State swimming pool
Bn 8900 Swimming pool temp
26
Object Type
Settable
Analog Value
Y
Analog Value
Y
Multistate Input
N
Multistate Input
Y
Analog Value
Y
Multistate Input
N
Object Type
Settable
Analog Input
N
Multistate Input
N
Analog Input
N
Multistate Input
N
Analog Value
Y
Multistate Input
N
Multistate Input
Y
Analog Value
Y
Analog Value
Y
Analog Value
Y
Multistate Input
N
Multistate Input
N
Analog Input
N
Multistate Input
N
Analog Input
N
Multistate Input
N
Analog Input
N
Multistate Input
N
Analog Input
N
Multistate Input
N
Analog Input
N
Multistate Input
N
Multistate Input
N
Multistate Input
N
Multistate Input
N
Multistate Input
N
Object Type
Settable
Analog Value
Y
Multistate Input
N
Multistate Input
N
Object Type
Settable
Analog Value
Y
Multistate Input
N
Multistate Input
N
Object Type
Settable
Analog Value
Y
Multistate Input
N
Analog Input
N
Limits
State Text Reference
55...95 °C
2...360 min
1...8
Status
1...3
Command
8...80 °C
1...301
StatusCodes
Limits
State Text Reference
0...140 °C
1...8
Status
0...140 °C
1...8
Status
10...600 min
1...8
Status
1...3
Command
0...30 °C
0...20 °C
8...95 °C
1...2
OnOff
1...8
Status
0...100 %
1...8
Status
0...100 %
1...8
Status
0...80 °C
1...8
Status
0...140 °C
1...8
Status
0...140 °C
1...8
Status
1...2
OnOff
1...8
Status
1...2
OnOff
1...8
Status
Limits
State Text Reference
8...95 °C
1...2
OnOff
1...8
Status
Limits
State Text Reference
8...95 °C
1...2
OnOff
1...8
Status
Limits
State Text Reference
8...95 °C
1...301
StatusCodes
0...100 °C
7724161 - 01 - 29072019