Herunterladen Inhalt Inhalt Diese Seite drucken

Short Circuit And Overload Behaviour; Fuses - Franke ACEX9001 Montage- Und Betriebsanleitung

Vorschau ausblenden Andere Handbücher für ACEX9001:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Use the following connecting cables:
Primary side (230 VAC)
Use only suitable installation cables in compliance with VDE (e.g. NYM 3×1.5 mm²).
Secondary side (7 VDC/ 12 VDC)
Use only original connection cable (FAR Order No. 2030010982).
Only for 7 V:
The resistance over the entire length of the cable (from the power supply to the
fitting) must be less than 3.4 ohms.
The cross-section must be selected according to the cable length.
13.4 Install one moisture-proof junction box per fitting (a).
13.5 Run an empty conduit (c; Ø 10 mm) from the moisture-proof junction box to the
flush-mounting cabinet.
13.6 Lay a 2-wire cable (b) in the empty conduit and slide it from the moisture-proof
junction box to the moisture-proof junction box.
13.7 Slide the connecting cable (d) for the sensor through the empty conduit (c).
The plug must be easily accessible for the fitting.
13.8 Connect the connecting cable (d) in the moisture-proof junction box.
13.9 Close the moisture-proof junction box with the protective cap (e).
13.10 Connect the extension cable to the fitting.

14. Short Circuit and Overload Behaviour

In the event of a short circuit during network operation, the output remains
disconnected. After a short circuit, the voltage thresholds specified for activation and
deactivation apply only after power has been deactivated on the primary side or after
the voltage threshold of 7 V has been reached.

15. Fuses

Caution!
The power supply is secured with a 1.6 AT/250 V fuse on the primary side. When
this fuse triggers, it is very probable that the device is defective.
- 8 -

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis