ELECTRICAL CONNECTION BETWEEN INDOOR AND OUTDOOR UNIT
ELECTRICAL REQUIREMENTS
Electrical wiring and connections should
be made by qualified electricians and in
accordance with local electrical codes
and regulation. The air conditioner units
must be grounded.
The air conditioner unit must be
connected to an adequate power outlet
from a separate branch circuit protected
by a time delay circuit breaker, as
specified on unit's nameplate.
Voltage should not vary beyond 10% of
the rated voltage.
An all-pole disconnection switch having a
contact separation of at least 3mm in all
poles should be connected in fixed wiring.
1. To connect the indoor unit to the
outdoor unit use the following electrical
cables.
2. Prepare the needed cables for
electrical connection.
3. Connect the cable ends to the
terminals of the indoor and outdoor
units.
4. Secure the multiple wire power cable
with the cable clamps.
ON-OFF TYPE(60Hz)
36/48/60 KBtu/h
Capacity
Power supply
Fuse Rating(ODU/IDU)
1- Power Cable (ODU)
2- Power Cable (IDU)
3- Interconnecting Cable
C1 N1
220V 1~ 60Hz
C1 N1
220V 1~ 60Hz
36K
30A / 16A
3 x 4.0mm
3 x 1.0mm
2 x 0.5mm
Indoor unit floor ceiling type
8
100
A
NOTES: The wire color code can be
selected by the installer.
The temperature of refrigerant
circuit will be high, please keep
the interconnection cable away
from the copper tube.
48K
Indoor & Outdoor
45A/16A
2
3 x 6.0mm
2
3 x 1.0mm
2
2 x 0.5mm
1
8
40
B
60K
50A/16A
2
2
3 x10.0mm
2
2
3 x 1.0mm
2
2
2 x 0.5mm