Herunterladen Inhalt Inhalt Diese Seite drucken

Troubleshooting - Rivacold MH-TH Serie Betriebs- Und Wartungsanleitungen

Verflüssigungssätze und split system mit schallgedämmtes gehäuse
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 51
12.

TROUBLESHOOTING

The compressor will not start and no humming sound
is heard
1
No power. Starter relay contacts open.
A
2
Thermal circuit breaker intervention.
3
Electrical connections loose or incorrect.
The compressor will not start (it makes a humming
sound) and the thermal circuit breaker intervenes
1
Electrical connections incorrect.
2
Low voltage at compressor.
3
Faulty start capacitor.
B
4
The relay does not close.
5
Electric motor – winding interrupted or in short
circuit.
The compressor starts but the relay does not open
1
Electrical connections incorrect.
2
Low voltage at compressor.
3
Relay locked closed.
C
4
Excessive discharge pressure.
5
Electric motor – winding interrupted or in short
circuit.
Thermal circuit breaker intervention
1
Low voltage at compressor (three-phase motor –
phase imbalance).
2
Thermal circuit breaker faulty.
3
Faulty run capacitor.
4
Excessive discharge pressure.
D
5
High suction pressure.
6
Compressor overheated - hot return gas.
7
Electric motor – winding interrupted or in short
circuit.
The compressor starts and runs at brief operating
cycles
1
Thermal circuit breaker.
2
Thermostat.
3
High-pressure
insufficient condenser cooling.
E
4
High-pressure switch intervention due to excess
refrigerant gas charge.
5
Low-pressure
insufficient refrigerant gas charge.
6
Low-pressure
expansion valve restriction or blockage.
Likely cause
switch
intervention
switch
intervention
switch
intervention
1
Check the line or replace the relay.
2
Check the electrical connections.
3
Tighten the connections or reconnect
wiring according to the wiring diagram.
1
Make the connections again.
2
Find and remove the cause.
3
Find the cause and replace the capacitor.
4
Find the cause and replace the relay if
necessary.
5
Replace the compressor.
1
Check the electric circuit.
2
Find and remove the cause.
3
Find and remove the cause.
4
Find the cause and replace the relay if
necessary.
5
Replace the compressor.
1
Find and remove the cause.
2
Check characteristics and replace if
necessary.
3
Find and remove the cause.
4
Check the ventilation and any restrictions
or obstructions in the system circuit.
5
Check the sizing of the system. Replace
the
condensing
powerful one if necessary.
6
Check the refrigerant charge; repair any
leaks and add gas if necessary.
7
Replace the compressor.
1
See the previous point (thermal circuit
breaker intervention).
2
Small differential: correct adjustment.
due
to
3
Check the correct operation of the fan
motor or clean the condenser.
4
Reduce the refrigerant charge.
due
to
5
Repair any leaks and add refrigerant gas
if necessary.
due
to
6
Replace the expansion valve.
Remedy
unit
with
a
more
MH TH Pag. 25
REV. 08 11/07
UK

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis