Parameter setting
Add-on radio modules
The ACT20 parameter setting software and respective parameter setting ca-
bles are used to set parameters for the radio modules and transmit installation
telegrams. After starting the ACT20 and logging on (user profile "Administra-
tor"), select the respective interface and activate the tab.
The installation process is shown on the heat meter display by means of the
current installation step ("Inst 8" to "Inst 1").
AMR & walk-by
• "Customer location" as freely selectable field (max. 8 digits)
Walk-by
• Start of transmission
• Type of readout
• Transmission delay
• Transmission-free days
Transmission of the cold quantity
In as far as the option "Cooling energy metering" is enabled on the heat meter,
the metering device transmits both heat metering and cooling energy metering
data.
For cooling energy metering, a second metering device with an ID number
calculated from the parameter FabNr of the heat meter +1 is shown in the
network node. This device is assigned the medium "Cold" in the data record.
E.g.:
ID heat
ID cold
The ERROR output is set under the following conditions:
1. If the module is not fitted to a calculator unit.
2. The calculator unit outputs its own ERROR message. This message can
be read off the LCD display of the calculator unit.
EN
104
A6V10816676_----_a
00.123.456